Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00024 Final2/14/20202/14/20202/14/2020 1:59:19 PMPPASS
Lock Box Is 1216 All Corections Will Be Done By 100 Phone #: ###-#### Inspection requested via web by jason shifflett corrections made final ok
ELE20-00105 Electrical Rough-In2/14/20202/14/20202/14/2020 1:11:51 PMPPASS
ceiling rough-in Phone #: ###-#### Inspection requested via web by Brandon Winters ceiling only ok to cover
ELE19-04145 Final2/12/20202/14/20202/14/2020 11:37:07 AMAFAIL
Please call Katie at ###-#### at least 30 minutes before arriving so she can meet you there. Thank you. Phone #: ###-#### Inspection requested via web by Winters LLC Cannot final project. Too many violation/ safety issues. (Exposed conductors in cab above range, Receps hanging from wall, open recep box, open 2gang in living. Cans have been added in living, kichen, bedroom and hall. Cover plates need installed on all switches controlling added lights.
ELE17-03788 Final2/10/20202/14/20202/14/2020 11:19:07 AMAPASS
Customer stated they would be home Friday morning. Their phone number is ###-####. Phone #: ###-#### Inspection requested via web by sam petterson Final ok
ELE19-02623 Final2/13/20202/14/20202/14/2020 10:58:08 AMAFAIL
Daryl- if possible call prior Phone #: ###-#### 406.12. Tamper resistant receps required.(Garage, 1 recep in garage hall, Kitchen island GFCI Left side) 210.8 Kitchen counter receps shall be GFCI protected. (Recep right side near Micro) 422.31 Disc of permenantly installed appliances( Water heater Lock outs 3 40A breakers) 356.30 LFNMC shall be secured 12in from box and every 3ft. (A/C whip)
ELE20-00534 Final2/13/20202/14/20202/14/2020 9:49:23 AMAPASS
This meter was replaced by the owner of the home but it is a rental so he couldn’t legally pull permit. I went and inspected his work and am pulling permit for job. It was already inspected and that is when he was told he would have to get an electrician. Phone #: ###-#### Inspection requested via web by Jake Cutler Meter base replacement final ok
ELE20-00534 Permanent Service2/14/20202/14/20202/14/2020 9:48:51 AMPPASS
This meter was replaced by the owner of the home but it is a rental so he couldn’t legally pull permit. I went and inspected his work and am pulling permit for job. It was already inspected and that is when he was told he would have to get an electrician. Phone #: ###-#### Inspection requested via web by Jake Cutler Meter base only. p/s u/g rec ok
ELE20-00024 Final2/13/20202/14/20202/14/2020 9:10:11 AMAFAIL
Its Ready Phone #: ###-#### Inspection requested via web by jason shifflett 110.26D Illumination shall be provided around all panel boards. 314.25 All boxes shall have cover plates. (Right of dryer)