BLD17-03210
| FIRE-Final Inspection | 2/14/2020 | 2/14/2020 | 2/14/2020 2:45:12 PM | P | FAIL |
|
|
The engineer's details for the notification height state the device is to be mounted between 80" and 96". All of the devices have been mounted above the stated limits.
Life safety Phone #: ###-#### Inspection requested via web by Amanda Farnsworth
|
BLD19-03703
| FIRE-Final Inspection | 2/14/2020 | 2/14/2020 | 2/14/2020 1:50:54 PM | P | PASS |
|
|
Life safety passed.
Brandon Phone #: ###-####
|
FIR19-00965
| INSP-Final Inspection | 2/13/2020 | 2/14/2020 | 2/14/2020 1:03:32 PM | P | FAIL |
|
|
Tested the two smoke detectors as shown on the plans but an additional detector is needed on the other side of the beam that splits the room in two.Provide as-builts prior to the next inspection.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD19-01927
| FIRE-Final Inspection | 2/13/2020 | 2/14/2020 | 2/14/2020 12:39:24 PM | P | FAIL |
|
|
Provide all of the small documents, provide letter from the architect for compliance with the 2018 IFC 1010.1.9.11 exception #3, repair the exit sign in the 4th floor conference room.
Phone #: ###-#### Inspection requested via web by Sam Reading
|
FIR20-00006
| INSP-Sprinkler Rough-in | 2/14/2020 | 2/14/2020 | 2/14/2020 11:52:47 AM | P | CANC |
|
|
Contact Ken Orahood ###-#### 30 min prior to RTC Insp Start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
FIR19-00702
| INSP-Sprinkler Rough-in | 2/14/2020 | 2/14/2020 | 2/14/2020 10:19:28 AM | P | PASS |
|
|
Fourth floor piping is ok for cover. See Mark Stumbaugh letter. Fourth floor rough to cover, ready any time. Call James when heading out there so he can meet you. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00816
| INSP-Sprinkler Rough-in | 2/13/2020 | 2/14/2020 | 2/14/2020 10:18:18 AM | A | PASS |
|
|
Rough/Tenting on Tower 1 ; 2, is passed. Piping can be covered.
call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00852
| INSP-Final Inspection | 2/14/2020 | 2/14/2020 | 2/14/2020 10:04:22 AM | P | PASS |
|
|
Permit finaled.
Inspection requested via web by Fire Scheduler
|
FIR20-00085
| INSP-Sprinkler Rough-in | 2/13/2020 | 2/14/2020 | 2/14/2020 9:55:26 AM | A | PASS |
|
|
Overhead rough passed, vertical pipe installed. Piping can be covered.
Call Anthony with any questions or concerns. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00100
| INSP-Final Inspection | 2/13/2020 | 2/14/2020 | 2/14/2020 9:24:21 AM | A | CANC |
|
|
Payton Phone #: ###-####
|
FIR20-00100
| INSP-Sprinkler Rough-in | 2/13/2020 | 2/14/2020 | 2/14/2020 9:24:06 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
Payton Phone #: ###-####
|