MEC20-00650
| Rough-in | 2/14/2020 | 2/14/2020 | 2/14/2020 3:15:07 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez - fireplace R/I ok
|
MEC20-00634
| Final | 2/13/2020 | 2/14/2020 | 2/14/2020 2:50:51 PM | P | PASS |
|
|
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - furnace only co ok
|
MEC19-04564
| Final | 2/11/2020 | 2/14/2020 | 2/14/2020 2:11:45 PM | P | PASS |
|
|
TML will be on site by 12-1pm to do necessary repairs. Thank you! Phone #: ###-#### Inspection requested via web by Denise Colin - furnace only co ok
|
MEC20-00458
| Final | 2/13/2020 | 2/14/2020 | 2/14/2020 2:00:13 PM | P | PASS |
|
|
Please call Tyler prior to arrival, a 30 minute pre-call would be great. ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby - furnace ac coil co ok
|
MEC20-00646
| Final | 2/13/2020 | 2/14/2020 | 2/14/2020 1:51:10 PM | P | NH |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - not home left notice on front door
|
MEC20-00619
| Final | 2/12/2020 | 2/14/2020 | 2/14/2020 1:40:12 PM | P | PASS |
|
|
Same day Install, it should be ready by afternoon.Please contact technician on site to be sure job is ready to have inspection done. Technician on Site Tony Hall ###-#### Phone #: ###-#### Inspection requested via web by Kelly Martin - furnace ac coil co ok
|
MEC20-00532
| Final | 2/14/2020 | 2/14/2020 | 2/14/2020 1:23:07 PM | P | FAIL |
|
|
PLEASE CALL HOMEOWNER ERIC WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery - furnace ac coil ok - need to see one more co sensor near single bedroom on west side of house
|
MEC20-00619
| Pressure Test | 2/12/2020 | 2/14/2020 | 2/14/2020 10:45:01 AM | A | CANC |
|
|
Please contact technician on site to be sure job is ready to have pressure test done. Technician on Site Tony Hall ###-#### Phone #: ###-#### Inspection requested via web by Kelly Martin - no 5lb flue pressure test witness needed
|
MEC20-00625
| Rough-in | 2/13/2020 | 2/14/2020 | 2/14/2020 10:30:56 AM | A | PASS |
|
|
Mechanical Gas Fireplace Rough-In Inspection Phone #: ###-#### Inspection requested via web by Dan Otero - fireplace R/I ok
|
MEC20-00570
| Pressure Test | 2/7/2020 | 2/14/2020 | 2/14/2020 10:10:20 AM | A | PASS |
|
|
Call 1 hour prior to meet you there Phone #: ###-#### Inspection requested via web by Rene Neumeyer - 20lb gas pressure test ok - adjust permit details to show log set and schedule final when ready
|
MEC20-00589
| Rough-in | 2/12/2020 | 2/14/2020 | 2/14/2020 9:50:09 AM | A | FAIL |
|
|
Please call ahead to Bruce when you are headed to the residence Phone #: ###-#### Inspection requested via web by Sarah Small - dryer venting is over 35' with all straight pipe and fittings included. Change termination location or remove fittings
|
MEC20-00591
| Final | 2/12/2020 | 2/14/2020 | 2/14/2020 9:49:49 AM | A | FAIL |
|
|
Please call ahead to Bruce when you are headed to the residence Phone #: ###-#### Inspection requested via web by Sarah Small - dryer venting is over 35' with all straight pipe and fittings included. Change termination location or remove fittings
|
MEC19-03802
| Conference | 2/13/2020 | 2/14/2020 | 2/14/2020 9:17:17 AM | A | PASS |
|
|
Tom Phone #: ###-#### - fireplace final ok - homeowner is working on gas line and had questions about gauges and testing. will disconnect gas line for range from main and test new and will also test gas line to log lighter
|
MEC20-00349
| Final | 2/11/2020 | 2/14/2020 | 2/14/2020 8:34:31 AM | A | PASS |
|
|
Please call Karen Vintar prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - furnace ac coil co ok
|
MEC19-03373
| Mec-Aging Inspection | 2/14/2020 | 2/14/2020 | 2/14/2020 8:01:36 AM | | FAIL |
|
|
Permit has not been active since being issued on 8-1-19. Schedule inspection with owner if work is completed. Permit will expire at the next mechanical aging inspection if not active.
|
MEC19-01814
| Mec-Aging Inspection | 2/14/2020 | 2/14/2020 | 2/14/2020 8:00:09 AM | | PASS |
|
|
WIP
|
MEC19-04673
| Pressure Test | 2/12/2020 | 2/14/2020 | 2/12/2020 12:40:27 PM | P | CANC |
|
|
Jenese Phone #: ###-#### Inspection cancelled from web by: Carlene Badillo
|