Inspections for the day of: Thursday, February 15, 2001.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD99-03148 FIRE-Alarm Testing2/14/20012/15/20012/15/2001 12:00:00 AMAFAIL
Scheduled by Inspector: 409 On 2/14/2001 1:49:04 PM 8:30 need lables for room detectors; stair tower debris and exit door blocked by dumpster; sprinkler head in electrical closet on 5th floor 2/15/2001 9:25:11 AM
FIR00-00604 INSP-Sprinkler Rough-in/Hydro2/15/20012/15/20012/15/2001 12:00:00 AMAPART
Added by Inspector: 409 On 2/15/2001 10:13:34 AM pressure test of room to ensure the FM 200 agent will maintain required levels after activation. passed test. Drake and Bruce with CM company present to witness test.
BLD99-03148 FIRE-Final Inspection2/15/20012/15/20012/15/2001 12:00:00 AMPPART
Added by Inspector: 409 On 2/15/2001 2:47:58 PM 5th floor complete
BLD00-03716 FIRE-Final Inspection2/15/20012/15/20012/15/2001 12:00:00 AMPPASS
Added by Inspector: 409 On 2/15/2001 4:07:17 PM
BLD99-02185 FIRE-Final Inspection2/15/20012/15/20012/15/2001 12:00:00 AMPPASS
Added by Inspector: 409 On 2/15/2001 4:07:49 PM