Inspections for the day of: Friday, February 15, 2002.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD01-01344 FIRE-Final Inspection2/14/20022/15/20022/15/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 02/14/2002 at 08:55:56. Contact: ###-####. sprinklers overspaced at new wall; need sprinkler in new storage closet; escutcheons needed 2/15/2002 12:38:45 PM
BLD01-03274 FIRE-Supply Line Hydro2/14/20022/15/20022/15/2002 12:00:00 AMACANC
###-#### NATHAN wrong type of inspection 2/15/2002 3:45:20 PM
BLD01-03274 FIRE-Final Inspection2/14/20022/15/20022/15/2002 12:00:00 AMAFAIL
###-#### NATHAN sprinklers obstructed in bathroon; too close to TX rooms 1 and 2; outside sidewall sprinkler deflector damaged/bent 2/15/2002 3:46:21 PM
BLD01-00234 FIRE-Alarm Testing2/14/20022/15/20022/15/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 02/14/2002 at 15:11:06. Contact: ###-####. See FIR01-00435 for notes 2/15/2002 12:35:47 PM
BLD01-02145 FIRE-Final Inspection2/14/20022/15/20022/15/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 02/14/2002 at 16:27:12. Contact: ###-####.
BLD01-01403 FIRE-Sprinkler Rough-in2/15/20022/15/20022/15/2002 12:00:00 AMANR
Scheduled by a contractor via Hello! on 02/15/2002 at 07:10:00. Contact: ###-####. called Bill Alexander about this and he said no inspections were to occur until he received additional plans; called contractor and he said he would call Bill 2/15/2002 12:35:10 PM
FIR01-00435 INSP-Alarm Testing2/15/20022/15/20022/15/2002 12:00:00 AMAFAIL
Scheduled by Inspector: 409 On 2/15/2002 12:33:58 PM tested all sprinkler control and tampers - okay; tested 4th floor and extender panel will not report trouble with battery loss; need to test dampers on 4th; no audibles on all floors 2/15/2002 12:37:46 PM