Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03605 ELE-Aging Inspection2/15/20052/15/20052/15/2005 12:00:00 AM PASS
ELE05-00430 Electrical Rough-In2/14/20052/15/20052/15/2005 12:00:00 AMAPART
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice walls ok 2/15/2005 8:18:36 AM
ELE05-00478 Electrical Rough-In2/14/20052/15/20052/15/2005 12:00:00 AMAPASS
###-#### - rich ok 2/15/2005 9:37:44 AM
ELE05-00478 Rough-In Permanent Service2/14/20052/15/20052/15/2005 12:00:00 AMAPASS
###-#### - rick r/i ok p/s u/g new ok 2/15/2005 9:37:59 AM
ELE05-00479 Rough-In Permanent Service2/14/20052/15/20052/15/2005 12:00:00 AMAPASS
###-#### - rick r/i ok p/s u/g new ok 2/15/2005 9:38:18 AM
ELE05-00480 Final2/14/20052/15/20052/15/2005 12:00:00 AMAPASS
Mitch-approve for cover; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok called needs bond bushing for emt at alarm cabinet 2/15/2005 9:01:32 AM
ELE05-00479 Electrical Rough-In2/14/20052/15/20052/15/2005 12:00:00 AMPPASS
###-#### - ok 2/15/2005 11:56:12 AM
ELE05-00341 Final2/15/20052/15/20052/15/2005 12:00:00 AMPNR
Phone #: ###-#### Internet Inspection Request from: Heather Packer
ELE04-01713 Final2/15/20052/15/20052/15/2005 12:00:00 AMPPART
FINAL INSPECTION FOR 2nd FLOOR ONLY @ RESIDENCE INN. THANK YOU; Phone #: ###-#### Internet Inspection Request from: Barry Kendall t/o for 2nd floor ok anop 2/15/2005 4:45:32 PM
ELE05-00283 Permanent Service2/15/20052/15/20052/15/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/15/2005 at 8:33:02 AM. Contact: ###-####. p/s o/h new ok 2/15/2005 1:02:36 PM
ELE04-03721 Permanent Service2/15/20052/15/20052/15/2005 12:00:00 AMPFAIL
Robert-call before you go out; Phone #: ###-#### Internet Inspection Request from: Jan Rice called left message 2/15/2005 1:04:52 PM cor. posted met owner 110.26(F)(1) clearence for p/s, 230.6 service mast inside, 230.28 support mast,230.24, clearence over roof, 250 needs grd rod grd or bond water system C O W 2/15/2005 2:42:51 PM
ELE05-00488 Rough-In Permanent Service2/15/20052/15/20052/15/2005 12:00:00 AMPPASS
terry ###-#### partial r/i p/s o/h rec. ok 2/15/2005 3:07:32 PM