Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00256 Final2/14/20052/15/20052/15/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tina Payne ok to final 2/15/2005 10:06:16 AM
ELE04-03417 Final2/14/20052/15/20052/15/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/14/2005 at 11:37:52 AM. Contact: ###-####. called contr to label subpanels to agree with meters. ok to final 2/15/2005 10:17:38 AM
ELE04-02595 Electrical Rough-In2/14/20052/15/20052/15/2005 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 2/14/2005 at 12:42:51 PM. Contact: ###-####. 4th fl so bath and soffits ok to cover 2/15/2005 8:32:48 AM
ELE04-03618 Final2/14/20052/15/20052/15/2005 12:00:00 AMAPASS
Al; Phone #: ###-#### Internet Inspection Request from: Jan Rice corrections made, ok to final 2/15/2005 9:06:44 AM
ELE05-00031 Final2/14/20052/15/20052/15/2005 12:00:00 AMANH
need final on kitchen and bathroom Internet Inspection Request from: Andy Rose called contr, he will reschedule 2/15/2005 8:43:40 AM
ELE04-04008 Final2/15/20052/15/20052/15/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/15/2005 at 7:13:40 AM. Contact: ###-####. ok to final 2/15/2005 7:53:03 AM
ELE05-00470 Temporary Service2/14/20052/15/20052/15/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn t/s u/g n ok 2/15/2005 9:36:57 AM
ELE04-03914 Final2/14/20052/15/20052/15/2005 12:00:00 AMPNH
Scheduled by a contractor via Hello! on 2/14/2005 at 8:24:51 AM. left card, nobody home 2/15/2005 12:07:12 PM
ELE05-00084 Final2/15/20052/15/20052/15/2005 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn called contr, left message. 314.43 nonmetallic box shall not have screws inside, 210.52(D) wash basin shall be within 3' of rcpt, left survey. 2/15/2005 3:22:57 PM
ELE05-00135 Final2/15/20052/15/20052/15/2005 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn ok to final 2/15/2005 4:24:53 PM
ELE04-03507 Electrical Rough-In2/15/20052/15/20052/15/2005 12:00:00 AMPFAIL
Ceiling inspection for phase 2 cover of ceiling.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas 358.30(A) emt shall be supported within 3' of box, 314.17(A) openings shall be closed (heater), 300.11(A) independent ceiling wires shall be identified, 300.11(2)(B) raceways shall not be used as support for non-electric equipment. Note: support wires for fixtures require min 2 wires for seismic 2/15/2005 2:12:31 PM
ELE05-00484 Final2/15/20052/15/20052/15/2005 12:00:00 AMPPASS
Please call prior to inspection mike ###-#### ok to final 2/15/2005 12:48:05 PM
ELE05-00486 Rough-In Permanent Service2/15/20052/15/20052/15/2005 12:00:00 AMPPASS
###-#### ric ok p/s u/g n ok 2/15/2005 3:10:49 PM