Inspections for the day of: Wednesday, February 15, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02686 ELE-Aging Inspection2/15/20062/15/20062/16/2006 2:45:28 PM DONE
see final
ELE05-03087 ELE-Aging Inspection2/15/20062/15/20062/15/2006 4:59:20 PM DONE
see final
ELE05-03150 ELE-Aging Inspection2/15/20062/15/20062/15/2006 4:58:12 PM DONE
suc
ELE06-00545 Final2/15/20062/15/20062/15/2006 4:03:41 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
ELE06-00548 Rough-In Permanent Service2/15/20062/15/20062/15/2006 3:08:45 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Rohl 314.16 boxes shall be of sufficient size to provide free space for all enclosed conductors, 300.4(D) nm cable shall be 1 1/4" from edge of framing member,312.5 all conductors entering enclosures shall have abrasion protection
ELE05-04326 Final2/15/20062/15/20062/15/2006 2:46:08 PMPPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
ELE06-00522 Permanent Service2/15/20062/15/20062/15/2006 1:37:31 PMPPASS
Eddie -- for reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left corr notice, BCC all wiring shall be brought up to code or further action will be taken(i.e. power could be turned off to structure). p/s u/g n ok
ELE06-00546 Final2/15/20062/15/20062/15/2006 1:11:54 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
ELE06-00509 Temporary Service2/15/20062/15/20062/15/2006 1:11:09 PMPFAIL
Scheduled by a contractor via Hello! on 2/15/2006 at 7:45:33 AM. Contact: ###-####. called contr, left corr notice, BCC job id sticker shall be posted, 250.24(A)(1) gec shall connect to grounded conductor terminal, 312.5 abrasion protection shall be provided for conductors entering enclosure
ELE05-03320 Final2/14/20062/15/20062/15/2006 10:28:55 AMACANC
Tom -- call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, he can't be there, wants to re-schedule
ELE05-02980 Electrical Rough-In2/14/20062/15/20062/15/2006 10:28:14 AMAPASS
chuck -- ###-#### walls only ok to cover, still need to run home runs and phone for ceilings, will see ltr
ELE06-00476 Final2/10/20062/15/20062/15/2006 9:43:05 AMANH
We wired 4 new ceiling lights from the existing wall switches. Thanks!!!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell called contr,left card, will re-schedule
ELE06-00174 Electrical Rough-In2/14/20062/15/20062/15/2006 9:23:53 AMAPART
Scheduled by a contractor via Hello! on 2/14/2006 at 3:13:50 PM. Contact: ###-####. ok to cover front part ceiling only
ELE06-00458 Rough-In Permanent Service2/15/20062/15/20062/15/2006 9:04:16 AMAFAIL
Scheduled by a contractor via Hello! on 2/15/2006 at 6:51:41 AM. Contact: ###-####. called contr, left message, 210.52(A)(1) recpt shall be installed such that no point is over 6' from another recpt in wall line.(dining room),300.4(D) nm cable shall be 1 1/4" from edge of framing member(front room, mbr), 314.17(C) nm cable sheath shall be minimum 1/4" inside box
ELE06-00447 Final2/14/20062/15/20062/15/2006 8:22:47 AMACANC
Posted wrong permit number on job ID tag ele06-00037 please call if you have questions.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil see rip
ELE06-00447 Rough-In Permanent Service2/15/20062/15/20062/15/2006 12:00:00 AMAFAIL
Posted wrong permit number on job ID tag ele06-00037 please call if you have questions.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil called contr left corr notice, 300.4(A) & (C) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 210.52(A)(1) recptacles shall be spaced so that no point along floor line is over 12' from recpt
ELE05-03087 Final2/15/20062/15/20062/15/2006 12:00:00 AMPPASS
looked at sign