Inspections for the day of: Wednesday, February 15, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00222 INSP-Final Inspection2/15/20062/15/20062/15/2006 4:33:49 PMPPASS
Permit finaled
FIR05-00562 INSP-Final Inspection2/14/20062/15/20062/15/2006 4:09:46 PMPFAIL
Need to forward flush the backflow preventor and install one additional hanger at the front entrance.
MIS04-00298 FIR-Final2/14/20062/15/20062/15/2006 4:08:32 PMPFAIL
I left Roxanne a copy of the original correction notice. No items have been corrected at this time. I went over the list with her again.
BLD05-01158 FIRE-Final Inspection2/14/20062/15/20062/15/2006 4:05:38 PMPFAIL
Per the plans the type I hood was to be deleted but per Roxanne she has been given a hood and is working towards getting it installed. I went over the notes with her showing the requirements for a FIR permit for the hood suppression system, the requirements for the air balance report and the K class fire extinguisher. The MIS04-00298 needs to be finaled.
FIR05-00571 INSP-Sprinkler Rough-in/Hydro2/15/20062/15/20062/15/2006 3:27:02 PMPFAIL
Provide support for the two 2" vertical pipes and for the vertical drop to the FDC. The sidewall heads are over spaced from the center beams on both sides and the beam exceeds 8" which requires protection beneath. The above ground hydro test passed.
FIR05-00312 INSP-Final Inspection2/14/20062/15/20062/15/2006 2:02:51 PMAPASS
Permit finaled
BLD04-00725 FIRE-Final Inspection2/15/20062/15/20062/15/2006 1:13:34 PMPPASS
Life safety finaled