ELE06-04055
| Electrical Rough-In | 2/15/2007 | 2/15/2007 | 2/15/2007 3:18:41 PM | P | CANC |
|
|
jerod Note: underground; Please call 1/2 hr prior to inspection Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to cover u/g
|
ELE07-00513
| Electrical Rough-In | 2/15/2007 | 2/15/2007 | 2/15/2007 2:23:12 PM | P | PASS |
|
|
Rough-in. Randy ###-#### Phone #: ###-#### called contr to add recpt to front, ric ok
|
ELE07-00535
| Temporary Service | 2/15/2007 | 2/15/2007 | 2/15/2007 1:45:14 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Victoria Beall t/s o/h n ok
|
ELE07-00459
| Permanent Service | 2/14/2007 | 2/15/2007 | 2/15/2007 12:06:35 PM | A | PASS |
|
|
Please call H.P. 1/2 hour before inspection. Phone #: ###-#### p/s exst meter pak n ok
|
ELE07-00525
| Rough-In Permanent Service | 2/14/2007 | 2/15/2007 | 2/15/2007 10:49:50 AM | A | FAIL |
|
|
hz ###-#### called, left corr notice,n BCC address shall be posted, NEC 300.5 u/g shall be 18" deep, 334.30 guy kit shall be installed at service, 210.52(A)(1) recpts shall be installed such that no point is over 6' from outlet, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member
|
ELE07-00467
| Electrical Rough-In | 2/15/2007 | 2/15/2007 | 2/15/2007 10:04:59 AM | A | PART |
|
|
Phone #: ###-#### corr made, ok to cover south part
|
ELE06-00320
| Electrical Rough-In | 2/14/2007 | 2/15/2007 | 2/15/2007 9:49:40 AM | A | CANC |
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Victoria Beall wrong type insp, see rip
|
ELE06-00320
| Rough-In Permanent Service | 2/15/2007 | 2/15/2007 | 2/15/2007 9:48:58 AM | A | CANC |
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, told owner to get room count on permit correct-19 rooms, ric ok, p/s u/g n ok
|
ELE06-04658
| Electrical Rough-In | 2/15/2007 | 2/15/2007 | 2/15/2007 8:58:27 AM | A | PASS |
|
|
ok to cover ceiling
|
ELE06-04658
| Electrical Rough-In | 2/15/2007 | 2/15/2007 | 2/15/2007 8:34:19 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 2/15/2007 at 7:19:47 AM. Contact: ###-####.
|
ELE07-00460
| Temporary Service | 2/14/2007 | 2/15/2007 | 2/15/2007 8:33:34 AM | A | CANC |
|
|
tony; Phone #: ###-#### Internet Inspection Request from: Victoria Beall wrong permit application, met elect, told to pull t./s permit, made conference, reviewed service and requirements for job
|
ELE07-00527
| Electrical Rough-In | 2/14/2007 | 2/15/2007 | 2/15/2007 7:58:56 AM | A | FAIL |
|
|
zane; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, BCC address shall be posted, job id sticker shall be posted, approved set of plans shall be on job
|