FIR06-00504
| INSP-Sprinkler Rough-in | 2/15/2007 | 2/15/2007 | 2/16/2007 10:57:03 AM | P | PART |
|
|
The OH piping hangers and seismic attatchments are okay for cover at the penthouse area only.
|
BLD06-03118
| FIRE-Final Inspection | 2/15/2007 | 2/15/2007 | 2/15/2007 3:59:32 PM | P | FAIL |
|
|
Missing address numbers, provide signage at the main entry/exit door, one emergency light did not operate, need to mount one additional PFE, need to final the project related FA permit.
|
FIR07-00004
| INSP-Final Inspection | 2/15/2007 | 2/15/2007 | 2/15/2007 3:57:19 PM | P | PASS |
|
|
Final fire sprinkler inspection passed, permit finaled.
|
BLD04-02464
| FIRE-Final Inspection | 2/13/2007 | 2/15/2007 | 2/15/2007 3:02:07 PM | A | NR |
|
|
Missing second pc. 401 FS escutcheons at building A1 canopy, provide knox box, scaffold at the perimeter of bld A1 must be removed prior to final.
|
FIR06-00946
| INSP-Final Inspection | 2/15/2007 | 2/15/2007 | 2/15/2007 2:52:23 PM | A | PASS |
|
|
Fire alarm permit finaled per previous field inspection completed by B. Johnson.
|
BLD05-03068
| FIRE-Final Inspection | 2/15/2007 | 2/15/2007 | 2/15/2007 2:34:17 PM | A | FAIL |
|
|
Final pending the secondary FD access roadway, also need to repair non-functional emergency lighting in the office area and repair door hardware at the N. exit door to the warehouse from the office area., noted approved plans are no longer on site for review.
|
BLD04-00941
| FIRE-Sprinkler Rough-in | 2/14/2007 | 2/15/2007 | 2/15/2007 1:38:15 PM | A | DEFR |
|
|
Inspection to be completed by B. Johnson.
|
FIR06-00651
| INSP-Final Inspection | 2/15/2007 | 2/15/2007 | 2/15/2007 1:36:46 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
BLD05-00849
| FIRE-Final Inspection | 2/14/2007 | 2/15/2007 | 2/15/2007 1:07:28 PM | A | FAIL |
|
|
Post missing max. occupant load signs at two rooms in the new addition, provide approved hardware at the door to the SE day room as circled on approved plans.
|
BLD06-03362
| FIRE-Final Inspection | 2/14/2007 | 2/15/2007 | 2/15/2007 1:05:48 PM | A | FAIL |
|
|
Missing exit signs and emergency lights at five locations as circled on approved plan set, missing items 2 and 3 on the list of requirements for the fire escape, post missing max. occupant load sign.
|
MIS07-00022
| FIR-Final | 2/14/2007 | 2/15/2007 | 2/15/2007 11:27:11 AM | A | FAIL |
|
|
Need to provide a current certification tag for the fire extinguisher and mount on the wall as discussed, secure loose junction box and cover bare wires at the loft area.
|