Inspections for the day of: Friday, February 15, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00026 INSP-Sprinkler Rough-in2/15/20082/15/20082/15/2008 4:02:38 PMPPASS
The underground piping from the stubout to the power pole is ok to cover except for the 22 degree fitting which will need a thrust block.
FIR07-01013 INSP-Sprinkler Rough-in/Hydro2/15/20082/15/20082/15/2008 3:29:35 PMPFAIL
The inspection was for above ground hydo tests. The dry system had lost pressure prior to me arriving. I also that the FDC was not being hydro as required. The wet system did have over 200 lbs. The fitter and I decided that all of the testing for buildings 1 and 2 as well as the rough in for buidling 2 will happen on wednesday.
BLD06-01694 FIRE-Final Inspection2/14/20082/15/20082/15/2008 3:27:22 PMAPASS
Life safety passed.
FIR07-00886 INSP-Sprinkler Rough-in/Hydro2/14/20082/15/20082/15/2008 2:32:12 PMACANC
Not ready for hydro test.
FIR07-00887 INSP-Sprinkler Rough-in/Hydro2/14/20082/15/20082/15/2008 2:28:15 PMACANC
Wrong inspection number called in.
FIR07-00949 INSP-Sprinkler Rough-in/Hydro2/14/20082/15/20082/15/2008 2:23:11 PMAPASS
underground hydro and flush passed
BLD07-03247 FIRE-Final Inspection2/14/20082/15/20082/15/2008 10:38:20 AMAPART
A temporary occupancy was given with sam rogers and dave hannimans permission until the racking permit has been taken care of. During the TOC period no product will be allowed to be stored on the racks.
BLD07-03232 FIRE-Final Inspection2/14/20082/15/20082/15/2008 9:42:40 AMAPASS
life safety passed. Fire extinguishers have been added in all four units as well as the operation of the existing fire alarms by the apartment maintenance personell.