FIR09-00082
| INSP-Final Inspection | 2/15/2011 | 2/15/2011 | 2/15/2011 2:45:21 PM | P | FAIL |
|
|
The tamper switches tested ok but came in on the same zone the the map indicated that the duct smoke detectors were on. So we tested two of the four duct smoke detectors and found that they havent been connected to the FACP. The duct detectors need to be connected to the FACP and the map corrected.
|
FIR11-00054
| INSP-Sprinkler Rough-in | 2/14/2011 | 2/15/2011 | 2/15/2011 2:32:06 PM | A | PASS |
|
|
The remaining sprinkler piping is ok to cover
|
BLD11-00249
| FIRE-Final Inspection | 2/9/2011 | 2/15/2011 | 2/15/2011 11:01:53 AM | A | FAIL |
|
|
Provide sticker at the main exit and repaire the warehouse emergency light.
|
BLD09-01711
| FIRE-Conference | 2/14/2011 | 2/15/2011 | 2/15/2011 9:59:29 AM | A | DONE |
|
|
I went over life safety requirements with the job superintendant. They included relocating the electric alarm bell to the new FDC location.
|
FIR10-00593
| INSP-Final Inspection | 2/14/2011 | 2/15/2011 | 2/15/2011 9:58:33 AM | A | PASS |
|
|
Permit finaled
|
FIR09-00082
| INSP-Final Inspection | 2/14/2011 | 2/15/2011 | 2/15/2011 8:26:12 AM | A | CANC |
|
|
I called Bryan at ###-#### twice before going to the project and once after I arrived at the project but did not contact him. I left messages. No inspection was performed.
|