Inspections for the day of: Wednesday, February 15, 2012.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00008 INSP-Sprinkler Rough-in2/15/20122/15/20122/16/2012 6:16:17 AMPPASS
Sprinkler modifications in the store room area are complete.
BLD11-01660 FIRE-Final Inspection2/13/20122/15/20122/16/2012 6:15:51 AMPPASS
Life safety passed.
BLD11-00836 FIRE-Final Inspection2/15/20122/15/20122/16/2012 6:15:30 AMPFAIL
Need the project related fire alarm and fire sprinkler permits addressed. Need the building address posted and the signage provided for the fire sprinkler and fire alarm control panel rooms posted. Need to verify that Chad mounted the knox box.
BLD11-01175 FIRE-Final Inspection2/14/20122/15/20122/16/2012 6:14:06 AMAPASS
life safety passed.
BLD11-00836 FIRE-Alarm Testing2/15/20122/15/20122/15/2012 10:37:31 AMPDONE
The fire alarm testing is complete except for a copy of the signal reports.
FIR11-00479 INSP-Final Inspection2/15/20122/15/20122/15/2012 10:09:22 AMPFAIL
Still need the zone map as discussed and signage on the bell and riser room door. Inspection rescheduled for tomorrow morning per conversation with CM company.
FIR11-00642 INSP-Final Inspection2/15/20122/15/20122/15/2012 10:07:21 AMPFAIL
Everything is complete except that to final the project I need the requested alarm report for monday and tuesday. Inspection rescheduled for tomorrow morning per conversation with CM company.
FIR11-00563 INSP-Sprinkler Rough-in2/14/20122/15/20122/15/2012 8:16:34 AMAFAIL
No inspection was performed. Called the contact twice and left one message. Walked all four floors of the construction area looking for fitters. Did not final anyone.