Inspections for the day of: Thursday, February 15, 2018.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00437 Permanent Service2/14/20182/15/20182/15/2018 1:52:19 PMPPASS
Ron Phone #: ###-####
p/s o/h rec ok
MIS18-00054 ELE-Conference2/15/20182/15/20182/15/2018 1:34:43 PMPFAIL
work w/o permits
BCC 4-05-18- Before any person installs or alters any wiring or equipment an electrical permit shall be obtained.
* Found new wiring at panel, outside light and AC unit dated 2017 with out permit.
Did not enter house.
Posted stop work order.
ELE17-02183 Electrical Rough-In2/15/20182/15/20182/15/2018 1:17:28 PMPPASS
Ground rods on north side near conduits for service to be buried under pavers.
Rough in ok cover
ELE18-00398 Electrical Rough-In2/14/20182/15/20182/15/2018 10:25:47 AMAPASS
Please call ahead, would like to meet on-site -
Jose Phone #: ###-####
Discussed 2 conference rooms, 1 is 220 sq. ft. 3 receptacles in center of room need 5 total in room, 1 is 180 sq. ft. floor receptacle not required but 3 in floor with 5 min required. Grid rough in ok cover
ELE18-00605 Electrical Rough-In2/14/20182/15/20182/15/2018 9:25:39 AMAPASS
andy ###-#### I''ll meet you there with a little advanced notice. thanks Phone #: ###-#### Inspection requested via web by Andy Derrick
Office dividing wall rough in ok cover
ELE17-04309 Final2/14/20182/15/20182/15/2018 8:57:29 AMAPASS
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok