ELE18-00437
| Permanent Service | 2/14/2018 | 2/15/2018 | 2/15/2018 1:52:19 PM | P | PASS |
|
|
Ron Phone #: ###-#### p/s o/h rec ok
|
MIS18-00054
| ELE-Conference | 2/15/2018 | 2/15/2018 | 2/15/2018 1:34:43 PM | P | FAIL |
|
|
work w/o permits BCC 4-05-18- Before any person installs or alters any wiring or equipment an electrical permit shall be obtained. * Found new wiring at panel, outside light and AC unit dated 2017 with out permit. Did not enter house. Posted stop work order.
|
ELE17-02183
| Electrical Rough-In | 2/15/2018 | 2/15/2018 | 2/15/2018 1:17:28 PM | P | PASS |
|
|
Ground rods on north side near conduits for service to be buried under pavers. Rough in ok cover
|
ELE18-00398
| Electrical Rough-In | 2/14/2018 | 2/15/2018 | 2/15/2018 10:25:47 AM | A | PASS |
|
|
Please call ahead, would like to meet on-site - Jose Phone #: ###-#### Discussed 2 conference rooms, 1 is 220 sq. ft. 3 receptacles in center of room need 5 total in room, 1 is 180 sq. ft. floor receptacle not required but 3 in floor with 5 min required. Grid rough in ok cover
|
ELE18-00605
| Electrical Rough-In | 2/14/2018 | 2/15/2018 | 2/15/2018 9:25:39 AM | A | PASS |
|
|
andy ###-#### I''ll meet you there with a little advanced notice. thanks Phone #: ###-#### Inspection requested via web by Andy Derrick Office dividing wall rough in ok cover
|
ELE17-04309
| Final | 2/14/2018 | 2/15/2018 | 2/15/2018 8:57:29 AM | A | PASS |
|
|
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|