Inspections for the day of: Wednesday, February 16, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03838 Final2/15/20052/16/20052/16/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/15/2005 at 3:07:34 PM. Contact: ###-####. ok to final 2/16/2005 10:45:01 AM
ELE04-02595 Electrical Rough-In2/15/20052/16/20052/16/2005 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 2/15/2005 at 4:35:03 PM. Contact: ###-####. 3rd floor barths south half, all stairwells ric ok 2/16/2005 8:09:09 AM
ELE04-03622 Final2/16/20052/16/20052/16/2005 12:00:00 AMADONE
builder hired new contractor to finish job. new permit 05-00484 finalled, so this permit ok to final also
ELE05-00460 Final2/15/20052/16/20052/16/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final 2/16/2005 9:28:31 AM
ELE05-00031 Final2/15/20052/16/20052/16/2005 12:00:00 AMAPASS
final on kitchen and bath Internet Inspection Request from: Andy Rose ok to final 2/16/2005 8:45:13 AM
ELE05-00411 Final2/15/20052/16/20052/16/2005 12:00:00 AMANR
Scheduled by a contractor via Hello! on 2/15/2005 at 10:06:24 AM. Contact: ###-####. contr didn't know approved for power. will finish temp hook-up and call for final later. 2/16/2005 9:13:35 AM
ELE04-03914 Final2/15/20052/16/20052/16/2005 12:00:00 AMPPASS
Pam; Phone #: ###-#### Internet Inspection Request from: Jan Rice told owner to put on covers in utility room, add afci for bedroom and found 1 wire not made up. ok to final 2/16/2005 1:46:35 PM
ELE04-03339 Final2/16/20052/16/20052/16/2005 12:00:00 AMPPASS
allan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made , ok to final 2/16/2005 12:28:19 PM
ELE05-00338 Final2/16/20052/16/20052/16/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/16/2005 at 8:29:35 AM. 314.20 boxes shall be within 1/4" of surface, 314.21 drywall shall be repaired at switch and outlets to less than 1/8", 314.25 boxes shall have covers installed, 314.23(C) boxes shall be rigidly installed in finished surface, 404(D) fixture over tub shall be listed for damp location, 406.8(C) recpt shall not be installed within bath tub area, 110.3(B) all equipment shall be listed, 110.26(A)(2) workspace shall be 30" wide in front of panel. 2/16/2005 4:41:48 PM
ELE05-00377 Permanent Service2/16/20052/16/20052/16/2005 12:00:00 AMPPASS
Chuck; Phone #: ###-#### Internet Inspection Request from: Jan Rice corrections made, p/s u/g exst pedestal ok 2/16/2005 12:12:01 PM
ELE05-00284 Electrical Rough-In2/16/20052/16/20052/16/2005 12:00:00 AMPPART
steve; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover conduit for elect room and nurse call stations 2/16/2005 4:33:40 PM
ELE04-03644 Final2/16/20052/16/20052/16/2005 12:00:00 AMPPASS
###-#### - allen ok to final 2/16/2005 1:18:45 PM
ELE05-00241 Electrical Rough-In2/14/20052/16/20052/15/2005 4:01:44 PMPCANC
Wall conver North End area, contact Matt, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters Inspection cancelled from web by: Wendy Waters
ELE05-00477 Final2/15/20052/16/20052/15/2005 2:11:24 PMACANC
Scheduled by a contractor via Hello! on 2/15/2005 at 2:00:59 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 15 2005 2:11PM.
ELE05-00477 Rough-In Permanent Service2/15/20052/16/20052/15/2005 2:10:53 PMACANC
Scheduled by a contractor via Hello! on 2/15/2005 at 2:00:21 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 15 2005 2:10PM.
ELE05-00407 Rough-In Permanent Service2/14/20052/16/20052/14/2005 12:27:43 PMACANC
Scheduled by a contractor via Hello! on 2/14/2005 at 11:47:37 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 14 2005 12:27PM.