BLD03-01845
| BLD-Final | 2/13/2006 | 2/13/2006 | | P | |
|
|
|
FIR05-00486
| INSP-Final Inspection | 2/15/2006 | 2/16/2006 | 2/17/2006 9:38:27 AM | P | FAIL |
|
|
"Office" room 905 is now a confrence room requiring visual notification, provide smoke detection at the restroom and telephone rooms, relocate SD in the lobby to afford proper coverage, the "closet" room lacks proper visual notification, provide an additional strobe to cover the blind spot at the east common area, dB level in the storage room is not adequate, the penthouse AV is non-functional on audio, provide resubmittals reflecting all modifications and required changes.
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 2/15/2006 | 2/16/2006 | 2/17/2006 9:31:31 AM | A | FAIL |
|
|
Today's inspection was for the 1st floor shell wet system at the north and east perimeter areas for future TI spaces and the start of the 24 hr. air test for 2nd floor dry system, one branch line is overspaced at the south end from a wall as noted on plans, heads in the pump room must be properly spaced for 130ft/2, changes in branch line routing at the electrical room to be shown on resubmittals with all other field changes on this floor, two TI spaces facing Broad St. have been completed prior to shell inspection at these locations, discussed hydro testing requirements for the first floor partial areas, began the 24 hr. air test of the 2nd floor dry system at 10:30 @ 43psi.
|
MIS06-00028
| FIR-Final | 2/16/2006 | 2/16/2006 | 2/16/2006 1:42:04 PM | P | PASS |
|
|
c/n items have been completed, life safety passed inspection.
|
BLD05-01669
| FIRE-Final Inspection | 2/15/2006 | 2/16/2006 | 2/16/2006 12:50:01 PM | | PART |
|
|
Fire life safety is acceptable pending resolution of item # 1 on the building fire code review notes for provision of one hour construction at the riser room or PIV installation. NOTE: if a PIV is installed, the valve must be electrically supervised for which an alarm permit is required.
2/17/06 - Approved by D. Hanneman for TOC based on AS and FA permit modifications having been submitted today for the Wall PIV modification and monitoring and written assurance from AS and FA contractors that work will be completed within 7 days. SLR
|
FIR05-00570
| INSP-Final Inspection | 2/16/2006 | 2/16/2006 | 2/16/2006 12:41:33 PM | P | PART |
|
|
The following items remain for final, need to provide for requirements of note #24 on plan review comments regarding one hour riser room construction or PIV installation, perform the forward flow test for the backflow prevention device, provide and attatch hydraulic calc. sticker to the riser.
|
FIR05-00460
| INSP-Final Inspection | 2/16/2006 | 2/16/2006 | 2/16/2006 12:35:23 PM | P | PASS |
|
|
UG fire supply line work finaled.
|
BLD05-01830
| FIRE-Final Inspection | 2/15/2006 | 2/16/2006 | 2/16/2006 12:33:36 PM | A | PASS |
|
|
Fire life safety passed inspection, visual indicator at the main entry/exit door to be installed for verification at final.
|
MIS06-00027
| FIR-Final | 2/15/2006 | 2/16/2006 | 2/16/2006 10:50:32 AM | A | FAIL |
|
|
Provide current certification tag on the fire extinguisher at the patio area, no storage is allowed in the stair enclosure (west side) obstructing the path of egress, repair door closure at the west fire door, provide a copy of the current inspection report for the fire sprinkler system.
|
FIR05-00330
| INSP-Sprinkler Rough-in/Hydro | 2/13/2006 | 2/16/2006 | 2/16/2006 9:51:21 AM | A | CANC |
|
|
WOULD LIKE IT AT 8AM IF POSSIBLE. LET ME KNOW.. Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
|
FIR05-00048
| INSP-Sprinkler Rough-in/Hydro | 2/13/2006 | 2/16/2006 | 2/16/2006 9:51:08 AM | A | CANC |
|
|
WOULD LIKE IT AT 8AM IF POSSIBLE. LET ME KNOW.. Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
|
FIR04-00166
| INSP-Alarm Testing | 2/13/2006 | 2/16/2006 | 2/16/2006 9:50:49 AM | A | CANC |
|
|
would like it at 8AM if possible let me know. Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
|
FIR06-00054
| INSP-Final Inspection | 2/15/2006 | 2/16/2006 | 2/16/2006 9:25:21 AM | A | PART |
|
|
Overhead sprinkler rough-in is good for cover at the drop ceiling areas, need to verify sheetrock panels at the full height wall separation between upright heads have been installed prior to final, also need ceiling tile and escutcheons installed, spare pendent heads in the head box.
|