Inspections for the day of: Friday, February 16, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00312 Electrical Rough-In2/16/20072/16/20072/16/2007 3:48:11 PMPPASS
ok to cover u/g, corr made
ELE07-00527 Rough-In Permanent Service2/16/20072/16/20072/16/2007 3:46:36 PMPFAIL
Scheduled by a contractor via Hello! on 2/16/2007 at 8:14:08 AM. Contact: ###-####. called, left corr notice, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members,210.70(A)(2)(b) lighting outlets shall be installed at outdoor entrances, 210.8(A) bath shall have recpt installed, BCC make-up shall be done
ELE06-03797 Final2/15/20072/16/20072/16/2007 2:53:03 PMPPASS
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final, signed struct card(only one available)
ELE07-00426 Permanent Service2/16/20072/16/20072/16/2007 2:12:14 PMPFAIL
Phone #: ###-#### called, left corr notice, BCC 4-05-33 (A)(B) equipment shall be listed and labelled by a nationally recognized testing laboratory, NEC 110.3(A)(1) suitability of equipment shall be evidenced by listing or labelling, 110 12(A) unused openings shall be closed, 200.9 terminal to which grounded conductor connected shall be identified white
ELE07-00324 Final2/16/20072/16/20072/16/2007 1:19:54 PMPFAIL
terry; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, NEC 110.26 (A) work space about equipment shall be maintained for 36" depth and 30" width
ELE07-00312 Electrical Rough-In2/16/20072/16/20072/16/2007 12:49:00 PMPFAIL
paul - underground ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, left corr notice, nec 344.26 & 352.26 there shall not be more than the equivalent of 4 quarter bends (360 degree total) between pull points, BCC all make-up shall be done- complete raceway sys before cover
ELE07-00541 Conference2/15/20072/16/20072/16/2007 10:17:51 AMADONE
william-- call 1st before insp -###-#### reviewed service and wiring requirements for shop
ELE06-04404 Final2/15/20072/16/20072/16/2007 9:26:24 AMAPASS
ok to final, signed occ card
ELE05-04325 Electrical Rough-In2/15/20072/16/20072/16/2007 8:28:30 AMAPART
JASON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover clgs anop 1st floor, some hard lid, some tile