ELE07-00312
| Electrical Rough-In | 2/16/2007 | 2/16/2007 | 2/16/2007 3:48:11 PM | P | PASS |
|
|
ok to cover u/g, corr made
|
ELE07-00527
| Rough-In Permanent Service | 2/16/2007 | 2/16/2007 | 2/16/2007 3:46:36 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/16/2007 at 8:14:08 AM. Contact: ###-####. called, left corr notice, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members,210.70(A)(2)(b) lighting outlets shall be installed at outdoor entrances, 210.8(A) bath shall have recpt installed, BCC make-up shall be done
|
ELE06-03797
| Final | 2/15/2007 | 2/16/2007 | 2/16/2007 2:53:03 PM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final, signed struct card(only one available)
|
ELE07-00426
| Permanent Service | 2/16/2007 | 2/16/2007 | 2/16/2007 2:12:14 PM | P | FAIL |
|
|
Phone #: ###-#### called, left corr notice, BCC 4-05-33 (A)(B) equipment shall be listed and labelled by a nationally recognized testing laboratory, NEC 110.3(A)(1) suitability of equipment shall be evidenced by listing or labelling, 110 12(A) unused openings shall be closed, 200.9 terminal to which grounded conductor connected shall be identified white
|
ELE07-00324
| Final | 2/16/2007 | 2/16/2007 | 2/16/2007 1:19:54 PM | P | FAIL |
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, NEC 110.26 (A) work space about equipment shall be maintained for 36" depth and 30" width
|
ELE07-00312
| Electrical Rough-In | 2/16/2007 | 2/16/2007 | 2/16/2007 12:49:00 PM | P | FAIL |
|
|
paul - underground ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, left corr notice, nec 344.26 & 352.26 there shall not be more than the equivalent of 4 quarter bends (360 degree total) between pull points, BCC all make-up shall be done- complete raceway sys before cover
|
ELE07-00541
| Conference | 2/15/2007 | 2/16/2007 | 2/16/2007 10:17:51 AM | A | DONE |
|
|
william-- call 1st before insp -###-#### reviewed service and wiring requirements for shop
|
ELE06-04404
| Final | 2/15/2007 | 2/16/2007 | 2/16/2007 9:26:24 AM | A | PASS |
|
|
ok to final, signed occ card
|
ELE05-04325
| Electrical Rough-In | 2/15/2007 | 2/16/2007 | 2/16/2007 8:28:30 AM | A | PART |
|
|
JASON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover clgs anop 1st floor, some hard lid, some tile
|