Inspections for the day of: Tuesday, February 16, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00123 FIRE-Final Inspection2/12/20102/16/20102/16/2010 4:01:03 PMPFAIL
Remove the thumbturn lock off of the exit door. Keyed hardware is ok. Provide single action hardware on the restroom door. Lever type that unlocks when the handle is pushed is ok. Provide plumbing rotection under the restroom sink for ADA compliance. This burn protection is required.
FIR09-00641 INSP-Alarm Testing2/16/20102/16/20102/16/2010 3:16:36 PMPCANC
Cancelled per Michael or ###-#### Rand Phone #: ###-####
BLD09-02009 FIRE-Final Inspection2/16/20102/16/20102/16/2010 1:47:38 PMPFAIL
Provide the three missing doors and their hardware and provide a fire alarm permit showing the door magnets at the main exit doors interconnected to the existing fire alarm system. The functionality of the door magnets was tested ok.
FIR09-00733 INSP-Final Inspection2/12/20102/16/20102/16/2010 12:50:33 PMAPASS
Permit finaled
BLD09-00461 FIRE-Final Inspection2/12/20102/16/20102/16/2010 11:52:56 AMAPASS
Life safety passed.
BLD09-01742 FIRE-Final Inspection2/16/20102/16/20102/16/2010 10:57:28 AMPPASS
Life safety passed. The access controlled egress doors 200 A & B, 204 A & C wil not be required to have the sensor on the egress side as per IFC 1008.1.3.4 and Dan Stuart and Jason Blaise's approval.
FIR09-00692 INSP-Final Inspection2/12/20102/16/20102/16/2010 10:55:21 AMAPASS
Permit finaled. The NAC wiring as shown on the plans is supposed to be 12ga but 14ga has been installed. The fire alarm vendor provided revised plans and calculations for the 14ga wire.
FIR09-00692 INSP-Sprinkler Rough-in/Hydro2/12/20102/16/20102/12/2010 2:52:40 PMACANC
Tom is the onsite contact his no. is ###-####. Inspection requested from web by: Shawna Gates Phone #: ###-#### Inspection cancelled from web by: Shawna Gates