FIR15-00235
| INSP-Supply line flush | 2/16/2016 | 2/16/2016 | 2/17/2016 8:15:34 AM | P | CANC |
|
|
Inspection request cancelled, assigned to wrong inspector.
|
BLD15-01092
| FIRE-Final Inspection | 2/16/2016 | 2/16/2016 | 2/16/2016 3:20:10 PM | P | PASS |
|
|
No fire sprinklers, fire/smoke/CO2 detectors are stand-alone, fire extinguishers are in place, point of contact Cory, phone number ###-#### will contact licensed contractor to have inspections on fire extinguishers current before final building inspection. Life ifre safety inspection passed/compete.
|
BLD15-04380
| FIRE-Final Inspection | 2/16/2016 | 2/16/2016 | 2/16/2016 2:55:00 PM | P | FAIL |
|
|
Fire extinguisher did not have a current inspection tag, fire extinguisher needs to be inspected and tagged by a licensed contractor. Exit sign needs to be serviced/repaired, did no stay illuminated with test button pressed, emergency egress light needs to be serviced/repaired, did not illuminate when test button pressed.
|
FIR16-00047
| INSP-Sprinkler Rough-in/Hydro | 2/16/2016 | 2/16/2016 | 2/16/2016 2:18:34 PM | P | PASS |
|
|
Rough to cover inspection passed/complete, all fire sprinkler piping for this permit approved for cover.
|
FIR15-00235
| INSP-Supply line flush | 2/16/2016 | 2/16/2016 | 2/16/2016 11:51:29 AM | P | DONE |
|
|
Underground fire main flush complete.
|
FIR15-00588
| INSP-Supply line flush | 2/15/2016 | 2/16/2016 | 2/16/2016 11:47:57 AM | P | CANC |
|
|
Inspection request was for underground hydro/flush, underground permit issued under FIR15-00235. Inspection request for underground flush/hydro under this FIR permit cancelled.
|
FIR15-00588
| INSP-Sprinkler Rough-in/Hydro | 2/15/2016 | 2/16/2016 | 2/16/2016 11:45:15 AM | A | CANC |
|
|
Inspection request was for underground hydro/flush, underground permit issued under FIR15-00235.
|
BLD15-03970
| FIRE-Final Inspection | 2/12/2016 | 2/16/2016 | 2/16/2016 9:24:29 AM | A | PASS |
|
|
Fire sprinklers complete (FIR15-00875 not attached to project related cases) fire alarms complete, fire extinguishers have current tags, orange cap on smoke detector located in the southeast section (smoke dampener detector) of tenant space needs to be removed before final building inspection. Final life fire safety inspection passed/complete.
|
FIR15-00875
| INSP-Final Inspection | 2/16/2016 | 2/16/2016 | 2/16/2016 9:19:40 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR15-00235
| INSP-Supply line flush | 2/12/2016 | 2/16/2016 | 2/15/2016 8:11:59 AM | A | CANC |
|
|
Suez was contacted to turn the water on at the site on Monday morning. Please contact Matt with questions. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|