Inspections for the day of: Friday, February 16, 2018.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00700 INSP-Sprinkler Rough-in2/15/20182/16/20182/16/2018 1:13:13 PMPFAIL
Check head spacing throughout project to veirfy proper distance from walls. Hangers will need to be adjusted/added throughout project. FDC piping will need to be completed before FDC can be covered. Cover for overhead fire sprinkler piping is not approved.
NAF18-00009 INSP-Final2/14/20182/16/20182/16/2018 11:10:19 AMADONE
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag, noted that main entry has thumb-turn deadbolt on existing door. Final life fire safey inspection for permitted area complete.
FIR18-00049 INSP-Sprinkler Rough-in2/15/20182/16/20182/16/2018 10:39:50 AMAPASS
Rough to ocver ibnspection for overhead fire sprinkler piping in area of work complete, approved for cover.