Inspections for the day of: Tuesday, February 17, 1998.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE98-00471 INSP - Final2/17/19982/17/19982/18/1998 12:00:00 AMPFAIL
02/17/98 315 - NU LOOK CAR WASH FOR A VACUUM \###-#### DON cor. posted T 300-5 conduit shall be 24 inches under area subject to veh traffic B.C.C. 4-5-60 vacuum not listed 250-114 EGC shallterminate to disconnect equip. grd bus also bonding jumper
ELE98-00474 INSP - Electrical Rough-In2/13/19982/17/19982/17/1998 12:00:00 AMAPART
02/17/98 315 - BILL ###-#### R\I P\S..trans by JMS.. cor. posted 210-52 outlets required in kit. right ok pocket door , and in MB left of bathroon door ps ok jf
ELE98-00476 INSP - Final2/13/19982/17/19982/17/1998 12:00:00 AMAFAIL
02/17/98 315 - ###-####\\SERVICE ONLY 100AMP cor. posted 310-16 provide proper overcurrent protection for conductors, 370-17& BCC 4-5-54 connector for cable j box, 250-81 terminate GEC withi of where metal piping enters house
ELE98-00479 INSP - Final2/13/19982/17/19982/17/1998 12:00:00 AMANH
02/17/98 315 - 200 AMP SERVICE nalc
ELE97-04023 INSP - Final2/12/19982/17/19982/17/1998 12:00:00 AMANR
02/17/98 315 - WADE ###-####-GET INTO HOUSE CALL ###-####-CHARLIE CONTRA notice posted 210-70 and BCC need to install 2 garage, and 1 outside bac light fixtures
ELE97-04446 INSP - Final2/13/19982/17/19982/17/1998 12:00:00 AMAPASS
02/17/98 315 - roger ###-#### final ok
ELE98-00482 INSP - Final2/13/19982/17/19982/17/1998 12:00:00 AMAFAIL
02/17/98 315 - TEMP POLE--ALLEN ###-####--ENTRY CODE TO SUB IS *1776 cor. posted 250-83(c) drive grd rod flush with grade
ELE98-00450 INSP - Final2/13/19982/17/19982/17/1998 12:00:00 AMAPASS
02/17/98 315 - DON ###-#### HOT TUB ok
ELE98-00486 INSP - Electrical Rough-In2/17/19982/17/19982/17/1998 12:00:00 AMPPASS
02/17/98 315 - ###-#### EMMITT 18rms 1a/c 200a
ELE98-00075 INSP - Electrical Rough-In2/17/19982/17/19982/17/1998 12:00:00 AMPCANC
02/17/98 315 - Scheduled by Hello!. Contact phone is [8662162]. no r/i needed final needed see added final inspection request
ELE98-00302 INSP - Final2/17/19982/17/19982/17/1998 12:00:00 AMPPASS
02/17/98 315 - temporary service steve ###-#### ok
ELE98-00316 INSP - Final2/17/19982/17/19982/17/1998 12:00:00 AMPPART
02/17/98 315 - ceiling insp debbie ###-#### all ceilings ok for cover no final jf
ELE98-00326 INSP - Final2/17/19982/17/19982/17/1998 12:00:00 AMPPASS
02/17/98 315 - ###-#### bernice final ok
ELE98-00482 INSP - Final2/17/19982/17/19982/17/1998 12:00:00 AMPPASS
TEMP ###-#### ALAN ok
ELE98-00474 INSP - Electrical Rough-In2/17/19982/17/19982/17/1998 12:00:00 AMPPASS
REINSPECTION ok 12rms 1a/c 200a