FIR04-00050
| INSP-Final Inspection | 2/13/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | A | FAIL |
|
|
Need ceiling tile installed 2/17/2004 11:19:42 AM
|
FIR04-00080
| INSP-Final Inspection | 2/13/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | A | CANC |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIR04-00102
| INSP-Final Inspection | 2/13/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | A | CANC |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIR04-00103
| INSP-Final Inspection | 2/13/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | A | CANC |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIR03-00448
| INSP-Sprinkler Rough-in/Hydro | 2/16/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | A | PART |
|
|
Sprinkler piping tie-ins from the second to the third floor are connected and ok for cover 2/17/2004 11:44:43 AM
|
FIR03-00678
| INSP-Final Inspection | 2/12/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | A | FAIL |
|
|
The system was not tested. The manual pull station is not between 10' and 20' per IMC 2/17/2004 10:10:10 AM
|
FIR04-00007
| INSP-Final Inspection | 2/12/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | P | PASS |
|
|
fire alarm finaled 2/17/2004 3:41:02 PM
|
BLD02-03083
| FIRE-Final Inspection | 2/13/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | P | FAIL |
|
|
Provide annual inspection tag for the fire extinguishers. Provide "Door to remain unlocked during business hours" sticker at the main entry/exit. Remove manual flush bolts per review note #7 on the main entry/exit. Remove thumb turn from the rear exit. Provide approved door hardware on the rear exit. Provide exit signs and emergency light in the basement per plans. Provide fire extinguisher in the basement with current inspection tag mounted at 48" above finish floor 2/17/2004 3:34:29 PM
|
FIR04-00063
| INSP-Sprinkler Rough-in/Hydro | 2/17/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | P | FAIL |
|
|
Resubmitted plans have not been issued yet. Resubmitted plans address 14.5 x 14.5 spacing of the sprinkler pendants 2/17/2004 1:14:05 PM
|
BLD02-03088
| FIRE-Final Inspection | 2/17/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | P | FAIL |
|
|
Need metal sample tubes in return air ducts since they exceed 1 1/2' in width. Third hvac unit that serves the 2nd story needs to have automatic shutdown per UMC since there is no separation between the 1st story and 2nd story systems 2/17/2004 4:00:03 PM
|
FIR03-00628
| INSP-Final Inspection | 2/17/2004 | 2/17/2004 | 2/17/2004 12:00:00 AM | P | PASS |
|
|
Permit finaled
|