ELE05-00418
| Final | 2/16/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | A | PASS |
|
|
Thank you, homeowner should be home. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok 2/17/2005 9:53:06 AM
|
ELE05-00143
| Final | 2/16/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/16/2005 at 10:52:35 AM. Contact: ###-####. ok card signed 2/17/2005 10:20:26 AM
|
ELE04-04021
| Final | 2/16/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | A | PASS |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok 2/17/2005 8:08:39 AM
|
ELE05-00155
| Electrical Rough-In | 2/16/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | A | PART |
|
|
ceiling cover inspection; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen counter area grid ok 2/17/2005 8:41:45 AM
|
ELE05-00510
| Electrical Rough-In | 2/16/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | A | FAIL |
|
|
alan ###-#### cor. posted met owner box fill 300.4, outside boxes not flush with finish this is a homeowner job general contractor called for electrical inspection 2/17/2005 9:36:25 AM
|
ELE04-03507
| Electrical Rough-In | 2/17/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | A | FAIL |
|
|
ceiling cover for grid in phase 2; Phone #: ###-#### Internet Inspection Request from: Joe Thomas cor. posted called 300.11(ABC) same corrections posted 12-09-04 2/17/2005 11:00:56 AM
|
ELE05-00068
| Electrical Rough-In | 2/17/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 2/17/2005 at 8:13:57 AM. Contact: ###-####. 2nd floor walls and hard ceilings ok 2/17/2005 2:42:15 PM
|
ELE05-00517
| Conference | 2/17/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | P | DONE |
|
|
###-#### mark ok 2/17/2005 1:30:15 PM
|
ELE04-03481
| Permanent Service | 2/17/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | P | FAIL |
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called left message,, 250.92(A)(3) shall install bond bushings on both ends of offset nipples between p/s and meterbase 2/17/2005 12:35:58 PM
|
ELE05-00521
| Electrical Rough-In | 2/17/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | P | FAIL |
|
|
###-#### steve cor. posted called , 314.17 needs cable connectors where cables enter boxes 1/2" KOs, replace all boxes with broken out clamps, 300.14 lenght of free conductor 2/17/2005 3:56:51 PM
|
ELE04-03507
| Electrical Rough-In | 2/17/2005 | 2/17/2005 | 2/17/2005 12:00:00 AM | P | PASS |
|
|
cover of ceiling grid in phase 2; Phone #: ###-#### Internet Inspection Request from: Joe Thomas 2/17/2005 1:30:07 PM
|