Inspections for the day of: Thursday, February 17, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00684 FIR-Aging Inspection2/17/20052/17/20052/17/2005 12:00:00 AM NR
Per tom work is in progress 2/17/2005 4:39:08 PM
FIR05-00088 INSP-Final Inspection2/16/20052/17/20052/17/2005 12:00:00 AMAPASS
Contact: Charles; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
FIR04-00811 INSP-Sprinkler Rough-in/Hydro2/16/20052/17/20052/17/2005 12:00:00 AMAPART
Second floor rough-in is ok but need armovers inspected when complete. Hardlid areas are ok to cover. Need resubmittals showing piping changes on second floor 2/17/2005 11:26:49 AM
FIR04-00761 INSP-Sprinkler Rough-in2/16/20052/17/20052/17/2005 12:00:00 AMAPART
Sprinkler piping over hardlid areas is ok to cover. Trapeze needs to be upsized per review notes. Underground supply piping is ok to cover. 2/17/2005 1:44:58 PM
FIR05-00046 INSP-Final Inspection2/16/20052/17/20052/17/2005 12:00:00 AMAPASS
###-#### - mick
BLD04-01537 FIRE-Final Inspection2/16/20052/17/20052/17/2005 12:00:00 AMAPASS
Life safety finaled 2/17/2005 8:10:24 AM
BLD04-03041 FIRE-Final Inspection2/16/20052/17/20052/17/2005 12:00:00 AMAFAIL
Door hardware not done, exit sign doesn't work. Asked contractor to check everything before reinspection 2/17/2005 9:31:09 AM
MIS05-00022 FIR-Final2/15/20052/17/20052/17/2005 12:00:00 AMPFAIL
Provide sprinkler pendant in closet. Provide ceiling tile at pendant in heating closet. Repair exit signs. Provide emergency lighting as discussed. Remove thumbturn from the northwest exit and provide panic hardware. Provide annual inspection for the hood and a K class fire extinguisher. 2/17/2005 4:27:15 PM
FIR05-00027 INSP-Final Inspection2/16/20052/17/20052/17/2005 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Rick Jackson
FIR04-00368 INSP-Sprinkler Rough-in/Hydro2/16/20052/17/20052/17/2005 12:00:00 AMPPART
Club house hydro test failed. 24 hour air test passed. 2/17/2005 3:20:32 PM
BLD04-02975 FIRE-Final Inspection2/17/20052/17/20052/17/2005 12:00:00 AMPPART
Tmeporary occupancy given. See sheet A2.01 for dificencies in emergency lighting and exit signs. Viking needs to finish three pendant heads. 2/18/2005 11:25:30 AM
FIR04-00694 INSP-Sprinkler Rough-in2/17/20052/17/20052/17/2005 12:00:00 AMPPASS
Ok to cover 2/18/2005 8:41:36 AM
BLD04-02763 FIRE-Final Inspection2/17/20052/17/20052/17/2005 12:00:00 AMPCANC
needs egress corridor finished 2/17/2005 3:58:33 PM
BLD04-02763 FIRE-Final Inspection2/17/20052/17/20052/17/2005 12:00:00 AMPCANC
needs egress corridor finished 2/17/2005 3:58:33 PM
BLD05-00079 FIRE-Final Inspection2/17/20052/17/20052/17/2005 12:00:00 AMPFAIL
Provide minimum 4" address numbers of contrasting colors and provide approved door hardware at the rear door. The thumbturn needs removed. 2/18/2005 12:33:39 PM
BLD03-03054 FIRE-Final Inspection2/17/20052/17/20052/17/2005 12:00:00 AMPFAIL
Provide annual inspection for the fire extinguishers, test emergency lighting, repair and test all exit signs. Reloceate the exit sign and change faces as discussed. Change exit stairs as discussed and noted by structural inspector 2/18/2005 10:10:41 AM