Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01845 BLD-Final2/13/20062/13/2006 P 
FIR05-00842 INSP-Sprinkler Rough-in2/16/20062/17/20062/17/2006 6:47:39 PMAFAIL
The approved stamped plans do not reflect the actual field installation, a drop ceiling is indicated on approved plans, however the space has been completed and installed with uprights for an OTS ceiling. As installed the uprights are blocked by beams and overspaced in certain locations, need to remove the uprights above the restroom hard lids, provide plan resubmittal reflecting accurate information regarding construction details and correct sprinkler layout prior to next inspection.
FIR05-00823 INSP-Sprinkler Rough-in2/16/20062/17/20062/17/2006 6:36:34 PMAFAIL
Heads are not cut in at any location for verification of spacing or installation method, the "work room" designated as OTS will require a drop ceiling or provide upright sprinkler protection for the entire space/cavity above all ceiling areas.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro2/17/20062/17/20062/17/2006 2:22:10 PMAPART
24 hour air test of the 2nd floor dry system passed.
BLD06-00084 FIRE-Conference2/16/20062/17/20062/17/2006 11:30:03 AMADONE
On site confrence to discuss construction modifications that may affect fire sprinkler coverage. Two locations at the west side will require changes in sprinkler coverage to avoid "cold solder" of heads that are now located too close together due to wall removal. A fire sprinkler permit is necessary to perform this work.