BLD09-00887
| FIRE-Conference | 2/16/2010 | 2/16/2010 | | P | |
|
|
Don H. Phone #: ###-####
|
FIR09-00593
| INSP-Final Inspection | 2/17/2010 | 2/17/2010 | 2/17/2010 4:48:09 PM | P | PART |
|
|
Fire alarm work tested acceptable, however the outside bell did not function during waterflow test.
|
FIR09-00594
| INSP-Final Inspection | 2/17/2010 | 2/17/2010 | 2/17/2010 4:45:21 PM | P | FAIL |
|
|
Waterflow switch and the outside bell are not operating correctly.
|
FIR09-00596
| INSP-Final Inspection | 2/17/2010 | 2/17/2010 | 2/17/2010 4:42:56 PM | P | NH |
|
|
No access at the time of inspection.
|
FIR09-00599
| INSP-Final Inspection | 2/17/2010 | 2/17/2010 | 2/17/2010 4:40:18 PM | P | PASS |
|
|
Fire alarm permit work approved for final, inspection passed.
|
FIR09-00598
| INSP-Final Inspection | 2/17/2010 | 2/17/2010 | 2/17/2010 4:35:01 PM | P | FAIL |
|
|
Sprinkler tamper switch at the main control valve initiated an alarm signal.
|
FIR09-00597
| INSP-Final Inspection | 2/17/2010 | 2/17/2010 | 2/17/2010 4:31:45 PM | P | FAIL |
|
|
Waterflow switch at the sprinkler riser failed to initiate an alarm signal via operation of the inspectors test valve.
|
FIR09-00595
| INSP-Final Inspection | 2/17/2010 | 2/17/2010 | 2/17/2010 4:27:38 PM | P | PASS |
|
|
Fire alarm work passed site testing, permit final approved.
|
BLD09-01971
| FIRE-Final Inspection | 2/16/2010 | 2/17/2010 | 2/17/2010 4:25:33 PM | A | FAIL |
|
|
See fire code review notes items #3 and #4 regarding signage and spill containment.
|
FIR10-00029
| INSP-Final Inspection | 2/16/2010 | 2/17/2010 | 2/17/2010 4:23:15 PM | A | PASS |
|
|
Fire alarm permit finaled.
|