Inspections for the day of: Wednesday, February 17, 2010.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00703 INSP-Final Inspection2/17/20102/17/20102/17/2010 4:09:11 PMPPASS
Permit finaled
FIR10-00009 INSP-Final Inspection2/17/20102/17/20102/17/2010 3:08:28 PMPPASS
Permit finaled. The NetCon was a 5.
BLD10-00162 FIRE-Final Inspection2/16/20102/17/20102/17/2010 3:07:24 PMPFAIL
Provide single action hardware for the double exit doors out the north side of the building. This is due to the west exit doors already having keyed hardware with the sticker and indicator. Provide one additional emergency light in the new open office area and the adjacent corridor just to the south. Also all of the exit signs need repaired.
FIR09-00494 INSP-Sprinkler Rough-in/Hydro2/17/20102/17/20102/17/2010 1:36:24 PMAPASS
Overhead hydro test passed.