FIR16-00045
| INSP-Sprinkler Rough-in/Hydro | 2/17/2016 | 2/17/2016 | 2/17/2016 2:31:57 PM | P | PASS |
|
|
Underground hydrostatic test (200psi for 2 hours) passed/complete. Remote FDC hydrostatic test (200psi for 2 hours) passed/complete
|
FIR15-00777
| INSP-Supply line flush | 2/16/2016 | 2/17/2016 | 2/17/2016 11:52:38 AM | P | DONE |
|
|
Underground main line flush complete.
|
FIR16-00007
| INSP-Final Inspection | 2/16/2016 | 2/17/2016 | 2/17/2016 10:20:22 AM | P | CANC |
|
|
Inspection request cancelled per conversation with Ken Phone #: ###-####, going to try and reschedule final alarm inspection to coincide with final fire sprinkler inspection.
|
FIR16-00083
| INSP-Final Inspection | 2/16/2016 | 2/17/2016 | 2/17/2016 9:59:03 AM | A | CANC |
|
|
Inspection request cancelled per conversation with Nathan, phone number ###-####, will reschedule for a later date.
|
BLD15-04532
| FIRE-Final Inspection | 2/17/2016 | 2/17/2016 | 2/17/2016 9:37:10 AM | P | PASS |
|
|
Fire sprinkler inspection complete (Orange glass bulb protectors to be removed before final builing inspection) , no fire alarm modifications, fire extinguisher will be installed at verified location with current inspection tag for final building inspection. Life fire safety inspection passed/complete.
|
FIR16-00059
| INSP-Sprinkler Rough-in/Hydro | 2/17/2016 | 2/17/2016 | 2/17/2016 9:34:10 AM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
BLD15-04380
| FIRE-Final Inspection | 2/16/2016 | 2/17/2016 | 2/17/2016 9:18:30 AM | A | PASS |
|
|
Previously notated items repaired. No fire sprinkler modifications, no fire alarm modifications, fire extinguishers have current inspection tag. Life fire safety inspection passed/complete.
|
FIR16-00033
| INSP-Sprinkler Rough-in | 2/16/2016 | 2/17/2016 | 2/17/2016 9:11:09 AM | A | PART |
|
|
Notated areas approved for cover with yellow high-lighter/red ink on city approved drawings. Area's inspected approved for cover.
|
BLD15-02063
| FIRE-Final Inspection | 2/16/2016 | 2/17/2016 | 2/17/2016 8:23:45 AM | A | PASS |
|
|
Previously noted items addressed/repaired. No fire sprinklers, no fire alarms, fire extinguishers have current inspection tags. Life fire safety inspection passed/complete.
|
FIR16-00009
| INSP-Sprinkler Rough-in | 2/15/2016 | 2/17/2016 | 2/16/2016 10:20:05 AM | A | PASS |
|
|
Rough to cover inspection complete for hardlids, approved for cover on hardlids only
|