ELE17-00403
| Permanent Service | 2/16/2017 | 2/17/2017 | 2/17/2017 3:50:30 PM | P | FAIL |
|
|
Randy is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen BCC 4-05-31- Unfused conductor shall not be ran on interior of walls. from meter base ran on interior of wall 7' to main breaker panel. 110.24- Available fault current shall be posted prior to permanent service inspection.
|
ELE17-00403
| Electrical Rough-In | 2/16/2017 | 2/17/2017 | 2/17/2017 2:42:55 PM | P | PASS |
|
|
wall Cover. Randy is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen Will check for labels on future solar conduits when permanent service inspection is done. Walls and hardlid rough in ok cover
|
ELE16-01946
| Electrical Rough-In | 2/16/2017 | 2/17/2017 | 2/17/2017 2:13:53 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Graham Estep Additional 1st floor walls rough in ok cover
|
ELE16-01946
| Conference | 2/17/2017 | 2/17/2017 | 2/17/2017 2:13:52 PM | P | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Graham Estep Discussed exposed MC cable below beams 1st floor and fire pump wiring. 330.12(1)- MC cable shall not be ran exposed to physical damage. Areas from floor to 8' are exposed to physical damage as per 300.5(D)(1). MC shall be enclosed in soffit for protection. I was able to grab standing on floor. 695.4(B)(2)- Individual sources of power. Overcurent device shall carry indefinitely the sum of locked rotor current of fire pump. Fire pump controller rated 25 hp with 25 hp pump. Mian breaker states may not trip until 1500 amp load reached.
|
ELE17-00257
| Electrical Rough-In | 2/15/2017 | 2/17/2017 | 2/17/2017 10:40:55 AM | A | PASS |
|
|
David Forbes ###-#### . I am trying to cancel the previous request for an inspection for 2/16. We actually need it on this day 2/17, not 2/16. Phone #: ###-#### Inspection requested via web by Samatha Solberg Checked print north wall and door no fire rating needed so did not require patching of low volt conduit down wall. Grid rough in ok cover
|
ELE16-04017
| Electrical Rough-In | 2/16/2017 | 2/17/2017 | 2/17/2017 10:04:59 AM | A | PASS |
|
|
underground for elec. room feeders ; communications. George Morris is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Feeder conduits from electrical room 30' towards main gear rough in ok cover
|
ELE17-00406
| Temporary Service | 2/16/2017 | 2/17/2017 | 2/17/2017 9:15:12 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Richard Gratiot t/s u/g n ok
|
ELE16-04117
| Final | 2/16/2017 | 2/17/2017 | 2/17/2017 8:37:27 AM | A | PASS |
|
|
Final inspection. Thank you Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|