Inspections for the day of: Friday, February 17, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00403 Permanent Service2/16/20172/17/20172/17/2017 3:50:30 PMPFAIL
Randy is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
BCC 4-05-31- Unfused conductor shall not be ran on interior of walls. from meter base ran on interior of wall 7' to main breaker panel.
110.24- Available fault current shall be posted prior to permanent service inspection.
ELE17-00403 Electrical Rough-In2/16/20172/17/20172/17/2017 2:42:55 PMPPASS
wall Cover. Randy is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Will check for labels on future solar conduits when permanent service inspection is done.
Walls and hardlid rough in ok cover
ELE16-01946 Electrical Rough-In2/16/20172/17/20172/17/2017 2:13:53 PMPPASS
Phone #: ###-#### Inspection requested via web by Graham Estep
Additional 1st floor walls rough in ok cover
ELE16-01946 Conference2/17/20172/17/20172/17/2017 2:13:52 PMPDONE
Phone #: ###-#### Inspection requested via web by Graham Estep
Discussed exposed MC cable below beams 1st floor and fire pump wiring.
330.12(1)- MC cable shall not be ran exposed to physical damage. Areas from floor to 8' are exposed to physical damage as per 300.5(D)(1). MC shall be enclosed in soffit for protection. I was able to grab standing on floor.
695.4(B)(2)- Individual sources of power. Overcurent device shall carry indefinitely the sum of locked rotor current of fire pump. Fire pump controller rated 25 hp with 25 hp pump. Mian breaker states may not trip until 1500 amp load reached.
ELE17-00257 Electrical Rough-In2/15/20172/17/20172/17/2017 10:40:55 AMAPASS
David Forbes ###-#### . I am trying to cancel the previous request for an inspection for 2/16. We actually need it on this day 2/17, not 2/16. Phone #: ###-#### Inspection requested via web by Samatha Solberg
Checked print north wall and door no fire rating needed so did not require patching of low volt conduit down wall.
Grid rough in ok cover
ELE16-04017 Electrical Rough-In2/16/20172/17/20172/17/2017 10:04:59 AMAPASS
underground for elec. room feeders ; communications. George Morris is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
Feeder conduits from electrical room 30' towards main gear rough in ok cover
ELE17-00406 Temporary Service2/16/20172/17/20172/17/2017 9:15:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Richard Gratiot
t/s u/g n ok
ELE16-04117 Final2/16/20172/17/20172/17/2017 8:37:27 AMAPASS
Final inspection. Thank you Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok