Inspections for the day of: Friday, February 17, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00227 ELE-Aging Inspection2/17/20172/17/20172/23/2017 12:04:36 PM DONE
still waiting for contractor to schedule...2nd attempt at contacting
ELE16-01924 Conference2/17/20172/17/20172/17/2017 2:11:44 PMPPASS
Micah Phone #: ###-####....

discussed new service to feed new panel for existing house circuits and panel for new addition....using existing recessed meter main and converting into junction box....new meter with main breaker on outside to feed new panels..explained could not have unfused conductors in wall...explored various options
ELE17-00388 Permanent Service2/17/20172/17/20172/17/2017 12:37:52 PMPPASS
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin....

p/s o/h rec ok
ELE17-00394 Final2/16/20172/17/20172/17/2017 12:18:15 PMPPASS
Call Miles with questions. ###-#### Phone #: ###-#### Inspection requested via web by Sheri Berry....

ok to final
ELE17-00057 Final2/16/20172/17/20172/17/2017 11:44:14 AMPNR
Final inspection please. Thank you. Phone #: ###-#### Inspection requested via web by Kyle Lott....

will call back in for monday 2/20/17
ELE17-00266 Electrical Rough-In2/16/20172/17/20172/17/2017 11:08:11 AMPPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe...

rough ok to cover
check for intersystem bond at sevice at final
p/s u/g n ok
ELE17-00267 Electrical Rough-In2/16/20172/17/20172/17/2017 11:06:55 AMPPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe...

rough ok to cover
check for intersystem bond at final at service
p/s u/g n ok
ELE17-00400 Conference2/16/20172/17/20172/17/2017 10:17:44 AMAPASS
Bryan Phone #: ###-####...

discussed whats needed to be done for rough in inspection...nailplating, stapling of wires...flat not on side...replace wire that sheathing been cut...remove old wiring...safe off existing wiring/proove not energized...ARC fault protection of all openings in bedroom-smoke detector, light, outlets....tamper resistant outlets to be installed
ELE17-00265 Final2/10/20172/17/20172/17/2017 9:32:30 AMAPASS
Insta hot circuit installed. Phone #: ###-#### Inspection requested via web by Randy Fletcher..

ok to final
ELE17-00195 Electrical Rough-In2/17/20172/17/20172/17/2017 9:10:47 AMAPASS
Please Sean Crawley call prior to arrival for access. Floor heat installation. Phone #: ###-#### Inspection requested via web by Patrick Paz....

ok to cover
ELE16-03455 Final2/16/20172/17/20172/17/2017 8:48:15 AMAFAIL
Garage code 7530 Phone #: ###-#### Inspection requested via web by Darryn Coburn..

1) exposed romex at furnace...334.15(B)
2) entry closet light to close to shelf...410.16(C)
3) exhaust fan in master shower shall have GFI protection...UL listing...110.3