Inspections for the day of: Wednesday, February 18, 1998.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD97-00348 INSP-Alarm Testing2/18/19982/18/19982/18/1998 12:00:00 AMAFAIL
tested elev. recall, sprink. tampers, pulls and detectors. strobes below min height, door jamb smokes not in FACP, fire ext mounted, sprink head problems in 1st floor lobby (within 6 ft/upright in pendant position)
BLD97-01243 INSP-Supply line flush2/17/19982/18/19982/18/1998 12:00:00 AMAPASS
###-#### SHELLY underground flush okay
BLD97-02877 INSP-Final Inspection2/17/19982/18/19982/18/1998 12:00:00 AMAFAIL
###-#### STEVE extinguisher and address needed.
BLD97-02881 INSP-Final Inspection2/17/19982/18/19982/18/1998 12:00:00 AMPPART
life safety ###-#### mobile mike no smoking sign and hazard placard.
BLD97-00040 INSP-Final Inspection2/17/19982/18/19982/18/1998 12:00:00 AMPFAIL
3:00 ###-#### retest elevator recall. add detector at FACP.