Inspections for the day of: Wednesday, February 18, 2004.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-03580 ELE-Aging Inspection2/18/20042/18/20042/18/2004 12:00:00 AM CANC
we do not inspect street lighting any more 2/19/2004 9:43:03 AM
ELE03-03581 ELE-Aging Inspection2/18/20042/18/20042/18/2004 12:00:00 AM PART
wsuc 2/24/2004 3:17:25 PM
ELE04-00365 Rough-In Permanent Service2/18/20042/18/20042/18/2004 12:00:00 AMAPASS
r/i ok corrections made contractor will call for final when power is hooked up
p/s o/h rec. ok
ELE04-00391 Final2/17/20042/18/20042/18/2004 12:00:00 AMAPART
warren ###-#### T O ok called contractor needs gfci for mixer recept, he will correct it today 2/18/2004 9:59:30 AM
ELE04-00365 Final2/17/20042/18/20042/18/2004 12:00:00 AMACANC
Call Dudley before going out to let you in, ###-#### ; Phone #: ###-#### Internet Inspection Request from: Dana Moyer see added r/i p/s 2/18/2004 9:25:33 AM
ELE04-00342 Electrical Rough-In2/17/20042/18/20042/18/2004 12:00:00 AMAFAIL
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called 300.11(C), 314.3 metal cable in plastic box, 314.16 handy boxes, 330.30 (C) strap within 12" of boxes 2/18/2004 8:57:44 AM
ELE04-00320 Electrical Rough-In2/17/20042/18/20042/18/2004 12:00:00 AMPFAIL
Steve -- please call for access. thanks.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes cor. posted met contractor300.4(A)(1)&(D), 210.52(B) 362.26&348.26 over 360 degrees of bends ENT, flex, 362.30&348.30 strap ENT&flex, 300.15,16 bushings for ENT&flex for low voltage, 210.11(C)(3) bathrm circuits 2/18/2004 2:40:08 PM
ELE04-00414 Rough-In Permanent Service2/18/20042/18/20042/18/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/18/2004 at 9:42:06 AM. Contact: ###-####. wired as duplex panel south unit is a sub panel r/i ok
p/s u/g new ok 2/18/2004 3:56:17 PM
ELE04-00401 Electrical Rough-In2/18/20042/18/20042/18/2004 12:00:00 AMPFAIL
house is vacant okay to go in, key under mat at front door.; Phone #: ###-#### Internet Inspection Request from: Andy Rose called do not cover posted remove outside back recept from small appliance circuit, 312.5(C), at p/s, clearence for power drop, 314.20 outside back light box shall be flush with siding 2/18/2004 1:13:56 PM