Inspections for the day of: Wednesday, February 18, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00683 FIR-Aging Inspection2/18/20042/18/20042/18/2004 12:00:00 AM PASS
will test when ready 2/18/2004 12:42:16 PM
BLD02-00369 FIRE-Final Inspection2/17/20042/18/20042/18/2004 12:00:00 AMAFAIL
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need signs on FACP and sprinkler room doors; signs in stairwells; extinguishers in lobby and fire pump room; lobby doors can't locked to trap people in lobby area; need extinguishers in penthouse rooms and on all floors; need smoke seals on all rated doors and they must latch; need to verify emergency lighting in corridors; stairwells and exit systems must be free of construction materials; update keys in knox box; complete elevator recall/shunt and sign-off 2/18/2004 3:42:30 PM
BLD02-00370 FIRE-Final Inspection2/17/20042/18/20042/18/2004 12:00:00 AMAFAIL
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need signs on FACP and sprinkler room doors; signs in stairwells; extinguishers in lobby and fire pump room; lobby doors can't locked to trap people in lobby area; need extinguishers in penthouse rooms and on all floors; need smoke seals on all rated doors and they must latch; need to verify emergency lighting in corridors; stairwells and exit systems must be free of construction materials; update keys in knox box; complete elevator recall/shunt and sign-off 2/18/2004 3:42:45 PM 2/18/2004 3:45:21 PM
BLD02-00371 FIRE-Final Inspection2/17/20042/18/20042/18/2004 12:00:00 AMAFAIL
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need signs on FACP and sprinkler room doors; signs in stairwells; extinguishers in lobby and fire pump room; lobby doors can't locked to trap people in lobby area; need extinguishers in penthouse rooms and on all floors; need smoke seals on all rated doors and they must latch; need to verify emergency lighting in corridors; stairwells and exit systems must be free of construction materials; update keys in knox box; complete elevator recall/shunt and sign-off 2/18/2004 3:43:01 PM 2/18/2004 3:44:55 PM
BLD02-00372 FIRE-Final Inspection2/17/20042/18/20042/18/2004 12:00:00 AMAFAIL
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need signs on FACP and sprinkler room doors; signs in stairwells; extinguishers in lobby and fire pump room; lobby doors can't locked to trap people in lobby area; need extinguishers in penthouse rooms and on all floors; need smoke seals on all rated doors and they must latch; need to verify emergency lighting in corridors; stairwells and exit systems must be free of construction materials; update keys in knox box; complete elevator recall/shunt and sign-off 2/18/2004 3:43:09 PM 2/18/2004 3:44:39 PM
BLD02-00373 FIRE-Final Inspection2/17/20042/18/20042/18/2004 12:00:00 AMAFAIL
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need signs on FACP and sprinkler room doors; signs in stairwells; extinguishers in lobby and fire pump room; lobby doors can't locked to trap people in lobby area; need extinguishers in penthouse rooms and on all floors; need smoke seals on all rated doors and they must latch; need to verify emergency lighting in corridors; stairwells and exit systems must be free of construction materials; update keys in knox box; complete elevator recall/shunt and sign-off 2/18/2004 3:43:29 PM 2/18/2004 3:44:23 PM
BLD02-00374 FIRE-Final Inspection2/17/20042/18/20042/18/2004 12:00:00 AMAFAIL
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need signs on FACP and sprinkler room doors; signs in stairwells; extinguishers in lobby and fire pump room; lobby doors can't locked to trap people in lobby area; need extinguishers in penthouse rooms and on all floors; need smoke seals on all rated doors and they must latch; need to verify emergency lighting in corridors; stairwells and exit systems must be free of construction materials; update keys in knox box; complete elevator recall/shunt and sign-off 2/18/2004 3:44:06 PM
BLD02-00375 FIRE-Final Inspection2/17/20042/18/20042/18/2004 12:00:00 AMAFAIL
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need signs on FACP and sprinkler room doors; signs in stairwells; extinguishers in lobby and fire pump room; lobby doors can't locked to trap people in lobby area; need extinguishers in penthouse rooms and on all floors; need smoke seals on all rated doors and they must latch; need to verify emergency lighting in corridors; stairwells and exit systems must be free of construction materials; update keys in knox box; complete elevator recall/shunt and sign-off 2/18/2004 3:42:54 PM 2/18/2004 3:45:06 PM
BLD04-00112 FIRE-Final Inspection2/17/20042/18/20042/18/2004 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 2/17/2004 at 12:55:42 PM. Fire not required to sign off on this permit; wrong type inspection called in; sent this inspection as a structural inspection to 425 2/17/2004 2:49:36 PM
FIR03-00598 INSP-Sprinkler Rough-in/Hydro2/17/20042/18/20042/18/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/17/2004 at 1:07:04 PM. Contact: ###-####. okay to cover hard lid areas; concealed combustible space around fireplace will require sprinklers; EQ at riser not completed; as-builts needed for minor changes; front canopy not sprinklered per plans as the construction of the canopy has changed - sidewall heads won't meet listing for smooth ceiling 2/18/2004 3:49:27 PM
FIR03-00139 INSP-Sprinkler Rough-in2/18/20042/18/20042/18/2004 12:00:00 AMPFAIL
performed walk through of all floors and the following need to be completed - signage on all valves, etc.; test jockey/pump operation with all supervised valves; elevator rooms need canopies on heads and at top of stairs; standpipe not extended to roof per plans; caps on all standpipe outlets; 4th floor room between elevator and stair has head at angle; 3rd floor trash room has tape on head; exposed CPVC pipe in 2nd floor meter room for drops and at pipe to dry sidewall; could not gain access to all rooms so this is not all inclusive 2/18/2004 1:03:20 PM