ELE09-02357
| Final | 2/17/2010 | 2/18/2010 | 2/18/2010 4:08:46 PM | P | PASS |
|
|
Please call Jeff at ###-#### if any problems. Thanks, Andrea. Inspection requested from web by: Andrea Creek Phone #: ###-#### x0000 ok to final
|
ESC09-00811
| General Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 1:55:21 PM | P | PASS |
|
|
looked ok
|
ESC09-00662
| General Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 1:54:41 PM | P | PASS |
|
|
looked ok
|
ESC08-00789
| General Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 1:54:01 PM | P | PASS |
|
|
looked ok
|
ESC09-00778
| General Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 1:53:19 PM | P | PASS |
|
|
looked ok
|
ESC09-00588
| General Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 1:52:40 PM | P | PASS |
|
|
looked ok
|
ESC09-00712
| General Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 1:52:03 PM | P | PASS |
|
|
looked ok
|
ELE09-01304
| Electrical Rough-In | 2/18/2010 | 2/18/2010 | 2/18/2010 1:47:18 PM | P | FAIL |
|
|
Inspection requested from web by: Randy Fletcher Phone #: ###-#### called, left correction notice, NEC 330.30(B) shall secure mc cable within 12" of box, 300.4(D) edge of cable shall be 1/14" from edge of framing member, 300.14 at least 6" free conductor shall be provided in box before splice, NOTE: shall repair switch entering electrical room, NOTE: corrections shall be made witin 5 working days or further action will be taken
|
ELE10-00305
| Electrical Rough-In | 2/18/2010 | 2/18/2010 | 2/18/2010 1:02:30 PM | P | PASS |
|
|
Inspection requested from web by: Joe Thomas Phone #: ###-#### corrections made, ok to cover
|
ELE10-00209
| Final | 2/17/2010 | 2/18/2010 | 2/18/2010 10:47:55 AM | A | PASS |
|
|
patio room / gate next to garage open no dog Inspection requested from web by: Jesse Fuentes Phone #: ###-#### ok to final
|
ELE10-00147
| Electrical Rough-In | 2/18/2010 | 2/18/2010 | 2/18/2010 10:32:05 AM | A | FAIL |
|
|
Fixed Conduits ready for underground inspection for hot tub Inspection requested from web by: Lynn Cable Phone #: ###-#### corrections not made, left correction notice, NEC 310.15(B)2(b) shall maintain conduit spacing, BCC shall not cover u/g before inspection, NOTE: corrections shall be made within 5 working days or further action will be taken
|
ELE09-02297
| Final | 2/17/2010 | 2/18/2010 | 2/18/2010 10:07:42 AM | A | PASS |
|
|
monument sign Inspection requested from web by: travis wilson Phone #: ###-#### ok to final, no esc this project
|
ELE09-02103
| Final | 2/17/2010 | 2/18/2010 | 2/18/2010 9:34:29 AM | A | PASS |
|
|
ready-cvr plates- lights- wr outlets tile work done owner still messing with walls but plates r there dw lock in place Inspection requested from web by: dennis mcneely Phone #: ###-#### ok to final
|
ELE09-02322
| Final | 2/17/2010 | 2/18/2010 | 2/18/2010 9:07:42 AM | A | PASS |
|
|
mike Phone #: ###-#### ok to final, no esc this project
|
ELE10-00285
| Electrical Rough-In | 2/17/2010 | 2/18/2010 | 2/18/2010 8:13:47 AM | A | PASS |
|
|
CONTACT: BRIAN GEE Inspection requested from web by: Deb Gooden Phone #: ###-#### ok to pour concrete encased electrode
|