BLD09-00887
| FIRE-Conference | 2/16/2010 | 2/16/2010 | | P | |
|
|
Don H. Phone #: ###-####
|
FIR10-00064
| INSP-Final Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 4:01:55 PM | P | PASS |
|
|
Fire sprinkler work passed both rough-in and final inspections, permit finaled.
|
BLD09-00287
| FIRE-Conference | 2/18/2010 | 2/18/2010 | 2/18/2010 4:00:29 PM | P | DONE |
|
|
Regarding exit discharge lighting levels at the east side of the building.
|
BLD09-01977
| FIRE-Final Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 3:59:10 PM | A | PASS |
|
|
C/N items completed.
|
FIR10-00010
| INSP-Final Inspection | 2/17/2010 | 2/18/2010 | 2/18/2010 3:57:57 PM | A | PART |
|
|
Fire alarm work tested satisfactory, final pending replacement of overdue batteries at the FACP.
|
FIR10-00008
| INSP-Final Inspection | 2/17/2010 | 2/18/2010 | 2/18/2010 3:50:56 PM | A | FAIL |
|
|
Operation of the tamper switch at a riser control valve did not report offsite, also noted inconsistency between items tested and signals recieved.
|
FIR10-00041
| INSP-Sprinkler Rough-in | 2/17/2010 | 2/18/2010 | 2/18/2010 3:45:17 PM | A | PART |
|
|
Fire sprinkler work per the permit scope passed rough-in inspection and is approved for cover at the drop ceiling.
|
FIR10-00056
| INSP-Sprinkler Rough-in | 2/17/2010 | 2/18/2010 | 2/18/2010 3:43:36 PM | A | PART |
|
|
Overhead fire sprinkler modifications are okay for cover at the drop ceilings within the tenant remodel area.
|