FIR09-00638
| FIR-Aging Inspection | 2/18/2010 | 2/18/2010 | 2/26/2010 4:02:56 PM | | NR |
|
|
work is in progress
|
BLD09-02109
| FIRE-Conference | 2/17/2010 | 2/18/2010 | 2/18/2010 4:04:06 PM | A | DONE |
|
|
Discussed the locations of several exit signs in relation to sprinkler pendants.
|
FIR09-00707
| INSP-Sprinkler Rough-in | 2/18/2010 | 2/18/2010 | 2/18/2010 3:48:16 PM | P | CANC |
|
|
Cancelled due to time constraints. Rescheduled with John Phone #: ###-#### for tomorrow morning.
|
FIR09-00641
| INSP-Final Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 3:20:45 PM | P | FAIL |
|
|
The FACP panel, phone line troubles, battery troubles, type 1 hood suppression system interconnection and the interconnections with the new fire alarm system passed. Also passed were the system smoke detectors located in the central wing. The system smoke detectors in the west wing did not function correctly due to one detector being smoked in a room activated the sounder base in a room across the hall. I let Micheal know that resubmittals will be required showing the additional door magnet interconnections.
|
FIR09-00440
| INSP-Final Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 3:17:38 PM | P | FAIL |
|
|
Due to time constraits I was unable to complete the entire inspection. The forward flush passed as well as the fire alarm interconnections. Verification of ceiling installation, canopy installation and any possible blocked heads due to light fixtures still needs to be completed.
|
FIR10-00047
| INSP-Sprinkler Rough-in | 2/18/2010 | 2/18/2010 | 2/18/2010 3:15:43 PM | P | PASS |
|
|
Phase I sprinkler piping ok to cover.
|
FIR10-00050
| INSP-Final Inspection | 2/17/2010 | 2/18/2010 | 2/18/2010 12:26:46 PM | A | FAIL |
|
|
Permit will be ready for a final when the ceiling tile has been installed. Sprinkler piping is ok for cover. I noted that there is another area not shown on the plans that is under construction where sprinkler modifications will be required. Todd was to follow up on this work.
|
FIR09-00708
| INSP-Sprinkler Rough-in | 2/17/2010 | 2/18/2010 | 2/18/2010 12:25:06 PM | A | PASS |
|
|
See the city approved plans marked with todays date for partial rough-in inspections on the last wet and dry systems.
|
FIR09-00708
| INSP-Sprinkler Rough-in/Hydro | 2/17/2010 | 2/18/2010 | 2/18/2010 12:23:59 PM | A | FAIL |
|
|
The last wet and dry system overhead hydro tests failed. There was visable leakage on the dry system.
|
BLD10-00035
| FIRE-Final Inspection | 2/17/2010 | 2/18/2010 | 2/18/2010 9:19:09 AM | A | PASS |
|
|
life safety passed
|
BLD09-02009
| FIRE-Final Inspection | 2/17/2010 | 2/18/2010 | 2/17/2010 3:15:12 PM | A | PART |
|
|
A temporary occupancy is being given with Scott Arellano's permission until the fire alarm quick permit is issued and finaled and the three missing doors/hardware are installed.
|