ELE14-02362
| Electrical Rough-In | 2/17/2015 | 2/18/2015 | 2/18/2015 3:12:03 PM | P | PASS |
|
|
We are requesting a ceiling cover inspection for tomorrow 2/18/15 in the pm. Our contact is Luke @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Ceiling cover ok, 5 rooms
|
ELE15-00151
| Electrical Rough-In | 2/18/2015 | 2/18/2015 | 2/18/2015 2:34:30 PM | P | PASS |
|
|
Can you please call ahead so I can make sure the house is unlocked for you if I am not there. Thanks, Mark Phone #: ###-#### Inspection requested via web by Mark Hennequin RI OK to cover, kitchen and bath area, basement romex will need strapping and securing for final
|
ELE15-00264
| Rough-In Permanent Service | 2/18/2015 | 2/18/2015 | 2/18/2015 2:13:06 PM | P | PASS |
|
|
Corrections have been made Phone #: ###-#### Inspection requested via web by Shaun Kirkman corrections made, RI OK, PS, UG, N, OK
|
ELE12-01598
| Final | 2/17/2015 | 2/18/2015 | 2/18/2015 1:43:40 PM | P | PASS |
|
|
Jennifer-call for access Phone #: ###-#### Final OK
|
ELE14-03505
| Final | 2/18/2015 | 2/18/2015 | 2/18/2015 1:27:41 PM | P | PASS |
|
|
Access from back ally Phone #: ###-#### Inspection requested via web by Brad Girard FInal OK
|
ELE15-00386
| Conference | 2/18/2015 | 2/18/2015 | 2/18/2015 1:10:16 PM | A | DONE |
|
|
Questions about outlet locations. Phone #: ###-#### Inspection requested via web by Eric Brown Discussed outlet placement in wet bar area, flat countertop with sliding window all the way to countertop. WHen window is fully open, outlets to each side will be within 2 foot of wall opening.
|
ELE14-03475
| Final | 2/18/2015 | 2/18/2015 | 2/18/2015 12:42:59 PM | A | NR |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn BCC 4.5.26 Trim out inspection, all items need to be working and installed.
|
ELE12-00913
| ELE-Aging Inspection | 2/18/2015 | 2/18/2015 | 2/18/2015 11:49:30 AM | | DONE |
|
|
Too busy
|
ELE12-02301
| ELE-Aging Inspection | 2/18/2015 | 2/18/2015 | 2/18/2015 11:48:49 AM | | DONE |
|
|
Too Busy
|
ELE14-03384
| Final | 2/17/2015 | 2/18/2015 | 2/18/2015 11:47:17 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn called Darryn 110.3.B listed or labeled equipment shall be installed in accordance with instructions, lockouts all fell off with panel cover 110.12 A Unused openings shall be closed, panel 210.5 Ungrounded conductors shall be permanently identified 422.11 e overcurrent protection shall not exceed that marked on appliance 408.4 Every circuit shall be legibly identified to its purpose, and accurately identified.
|
ELE14-03544
| Rough-In Permanent Service | 2/17/2015 | 2/18/2015 | 2/18/2015 11:01:35 AM | A | PASS |
|
|
Kevin Phone #: ###-#### RI OK, PS, UG, N< OK
|
ELE14-03447
| Electrical Rough-In | 2/17/2015 | 2/18/2015 | 2/18/2015 10:34:14 AM | A | PASS |
|
|
Rough in inspection for floor heat - You can call Darrel Kubik @ ###-#### Phone #: ###-#### Inspection requested via web by Charmel Kubik Floor heat cable, upstairs master bath OK to cover
|
ELE14-02968
| Final | 2/17/2015 | 2/18/2015 | 2/18/2015 10:26:33 AM | A | FAIL |
|
|
Fred// please call before Phone #: ###-#### Met homeowner, upstairs receptacles required to be tamper resistant, all dwellings.
|
ELE15-00198
| Final | 2/17/2015 | 2/18/2015 | 2/18/2015 10:15:08 AM | A | FAIL |
|
|
back shop is open Phone #: ###-#### Inspection requested via web by David Nelson contractors voice mail was full, could not leave message 408.4 every circuit shall be legibly identified for its purpose 334.12 B 4 NM cable not permitted in wet or damp locations 422.11 overcurrent protections device rating shall not exceed rating marked on the appliance 312.5 C cable shal l be secured to the cabinet
|
ELE14-03296
| Final | 2/18/2015 | 2/18/2015 | 2/18/2015 9:39:19 AM | A | FAIL |
|
|
Garage code 3283 Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov BCC 4.05.26 Trim out inspections, all items are to be working, outlet in master bath has no power BCC
|
ELE15-00412
| Temporary Service | 2/16/2015 | 2/18/2015 | 2/18/2015 8:36:53 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt TS, UG, N, OK
|