Inspections for the day of: Wednesday, February 18, 2015.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00708 INSP-Sprinkler Rough-in2/18/20152/18/20152/19/2015 4:39:35 PMPPART
Rough-in inspection for the 4th floor area F living units completed.
BLD14-02773 FIRE-Final Inspection2/18/20152/18/20152/18/2015 3:59:11 PMPPASS
Fire life safety finaled.
FIR14-00866 INSP-Sprinkler Rough-in2/13/20152/18/20152/18/2015 3:17:09 PMAPART
Completed initial rough-in for the 2nd floor living units as annotated on approved plans. Items incude; missing sprinker at closet, overspaced coverage, sprinkler too close to ceiling fan, noted two unprotected concealed spaces, incorrect type of head at the janitors room.
FIR14-00815 INSP-Sprinkler Rough-in2/17/20152/18/20152/18/2015 3:09:59 PMAPART
Requesting UG/Flush inspection. Jeff C is your contact. Please call 1/2 prior to inspection. Phone #: ###-#### Inspection requested via web by Stan Beus * *UG fire supply line flush completed satisfactory* Note- UG permit work attatched to FIR14-00477.
FIR14-00862 INSP-Final Inspection2/18/20152/18/20152/18/2015 3:05:49 PMAPASS
As-built plans accepted. Modified scope of work to include the new HVAC unit and duct detector tested satisfactory. Permit finaled.
FIR15-00070 INSP-Sprinkler Rough-in2/18/20152/18/20152/18/2015 3:04:08 PMAPART
Fire sprinkler work okay for cover at the sheetrock lid ceilings. Grid ceilings and heads above the sales areas are not yet complete.
FIR15-00065 INSP-Sprinkler Rough-in2/18/20152/18/20152/18/2015 3:01:02 PMAPART
Verified adjusted coverage at the 15th floor per previous inspection notes.