Inspections for the day of: Wednesday, February 18, 2015.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00362 Final2/16/20152/18/20152/19/2015 9:53:55 AMAFAIL
Phone #: ###-#### Inspection requested via web by Thaniel Bishop 210.8(A)(2) All 15 and 20 ampere 120 volt garage receptacles require GFCI protection. Photovoltaic monitoring equipment. NEC 690.35 (F) Warning Label Article 690.35 Ungrounded Photovoltaic Power Sytems under review, NEC 690.47 Grounding Electrode System
ELE14-01814 Electrical Rough-In2/18/20152/18/20152/18/2015 1:58:36 PMPPASS
Rough-in inspection hard lid ceilings ''D'' Commons rooms: 116 ; 117. IL area ''E'' corridor and support room walls rooms: E151, E152, E153, E154,E155, E251, E252, E253, E254,E255 E351, E352, E353, ; E354,E355 Building permit # BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover as noted
GCE15-00027 GCE-Rough-In2/18/20152/18/20152/18/2015 11:35:05 AMPPASS
Rick ###-#### correction completed, rough-in ok cover floor heat cabling in master bath
GCE15-00027 GCE-Rough-In2/17/20152/18/20152/18/2015 9:36:31 AMAFAIL
Rick ###-#### Floor heat cable spacing not installed to manufactures requirements.Not more than 6 consecutive spacing of 1 1/2