FIR02-00338
| INSP-Sprinkler Rough-in/Hydro | 2/18/2003 | 2/19/2003 | 2/19/2003 12:00:00 AM | A | PART |
|
|
doug; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie started 24 hr air test at 43 psi. 2/19/2003 10:27:25 AM
|
BLD02-00826
| FIRE-Conference | 2/18/2003 | 2/19/2003 | 2/19/2003 12:00:00 AM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung met with Jack and told him he needs to submit plans for the sprinkler work and alarm work; needs annual inspection on sprinkler system 2/19/2003 2:46:11 PM
|
BLD02-01958
| FIRE-Final Inspection | 2/18/2003 | 2/19/2003 | 2/19/2003 12:00:00 AM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD02-01532
| FIRE-Final Inspection | 2/18/2003 | 2/19/2003 | 2/19/2003 12:00:00 AM | P | FAIL |
|
|
SCOTT; Phone #: ###-#### Internet Inspection Request from: Darla Downs FACP's aren't talking to each other; need supervised tamper switches; need horn/strobes working per NFPA 72 2/19/2003 5:06:28 PM
|
FIR03-00031
| INSP-Final Inspection | 2/19/2003 | 2/19/2003 | 2/19/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 2/19/2003 at 11:30:02 AM. Contact: ###-####.
|