Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00710 FIR-Aging Inspection2/19/20042/19/20042/19/2004 12:00:00 AM PASS
Per Billy this will be scheduled for first week of March 2/19/2004 10:26:27 AM
FIR03-00153 INSP-Final Inspection2/17/20042/19/20042/19/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/17/2004 at 6:22:16 PM. Contact: ###-####. strobes not within 15 ft from ends of corridors; need to test devices/notification 2/19/2004 3:46:25 PM
FIR03-00154 INSP-Final Inspection2/17/20042/19/20042/19/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/17/2004 at 6:23:06 PM. Contact: ###-####. strobes not within 15 ft from ends of corridors; need to test devices/notification 2/19/2004 3:47:02 PM
FIR03-00155 INSP-Final Inspection2/17/20042/19/20042/19/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/17/2004 at 6:23:44 PM. Contact: ###-####. strobes not within 15 ft from ends of corridors; need to test devices/notification 2/19/2004 3:47:34 PM
FIR03-00156 INSP-Final Inspection2/17/20042/19/20042/19/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/17/2004 at 6:24:10 PM. Contact: ###-####. strobes not within 15 ft from ends of corridors; need to test devices/notification 2/19/2004 3:48:07 PM
FIR03-00157 INSP-Final Inspection2/17/20042/19/20042/19/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/17/2004 at 6:24:40 PM. Contact: ###-####. strobes not within 15 ft from ends of corridors; need to test devices/notification 2/19/2004 3:48:36 PM
FIR03-00158 INSP-Final Inspection2/17/20042/19/20042/19/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/17/2004 at 6:25:05 PM. Contact: ###-####. strobes not within 15 ft from ends of corridors; need to test devices/notification 2/19/2004 3:45:13 PM
FIR03-00159 INSP-Final Inspection2/17/20042/19/20042/19/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/17/2004 at 6:25:42 PM. Contact: ###-####. need to test sprinkler flows/pump/tampers and notification on first floor; devices not completed in laundry room 2/19/2004 3:44:38 PM
FIR04-00062 INSP-Conference2/19/20042/19/20042/19/2004 12:00:00 AMPPART
This is Robs Cell Phone Thanks Rick, Have a great day; Phone #: ###-#### Internet Inspection Request from: Terry Owsley met with Rob about strobe placement at pool area and it will have to be installed at plan location or hang strobe from ceiling; elevator smoke detector to comply with state inspection as the two floor elevator has open lobbies to both floors 2/19/2004 1:59:58 PM
BLD03-00830 FIRE-Final Inspection2/19/20042/19/20042/19/2004 12:00:00 AMPPASS
###-#### aaron
FIR03-00427 INSP-Sprinkler Rough-in/Hydro2/19/20042/19/20042/19/2004 12:00:00 AMPPASS
Final inspection for China Blue; Phone #: ###-#### Internet Inspection Request from: Robert Bailey
FIR03-00427 INSP-Final Inspection2/19/20042/19/20042/19/2004 12:00:00 AMPPASS
final okay