Inspections for the day of: Tuesday, February 19, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Kinnear
TitleELE-INSPECTOR
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00104 Final2/19/20082/19/20082/19/2008 5:01:10 PMPFAIL
tim Phone #: ###-#### nec210.52 counter space kitchen note the homer owner changed from the print & they neede 2 receps. for 5ft counter one on each end will be ok.
ELE07-04238 Electrical Rough-In2/18/20082/19/20082/19/2008 4:18:58 PMPPASS
Scheduled by a contractor via Hello! on 2/18/2008 at 2:33:59 PM. Contact: ###-####. - ok cover ri
ELE07-03591 Electrical Rough-In2/19/20082/19/20082/19/2008 3:44:43 PMPPASS
bill Phone #: ###-#### ok cover ri note service not ready needs 2inch imc or rigid conduit thru roof
ELE07-03592 Electrical Rough-In2/19/20082/19/20082/19/2008 2:35:35 PMPPASS
bill Phone #: ###-#### ok cover ri
ELE07-03592 Permanent Service2/19/20082/19/20082/19/2008 2:35:14 PMPPASS
bill Phone #: ###-#### p/s o/h n ok
ELE08-00368 Electrical Rough-In2/19/20082/19/20082/19/2008 1:01:25 PMPPASS
Scheduled by a contractor via Hello! on 2/19/2008 at 8:12:48 AM. Contact: ###-####. ok ri
ELE08-00368 Final2/19/20082/19/20082/19/2008 1:01:03 PMPPASS
Scheduled by a contractor via Hello! on 2/19/2008 at 8:12:48 AM. Contact: ###-####. ok final
ELE08-00219 Final2/18/20082/19/20082/19/2008 10:50:02 AMAPASS
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok final no card available to sign
ELE08-00116 Electrical Rough-In2/18/20082/19/20082/19/2008 10:48:49 AMAPASS
Scheduled by a contractor via Hello! on 2/18/2008 at 8:11:11 AM. Contact: ###-####. ok cover under slab conduits & boxes
ELE08-00248 Final2/15/20082/19/20082/19/2008 9:37:08 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok final
ELE08-00311 Electrical Rough-In2/15/20082/19/20082/19/2008 9:12:54 AMANR
Scheduled by a contractor via Hello! on 2/15/2008 at 4:39:57 PM. Contact: ###-####. conf. nec400.8 (bug zappers) & no cable shall be supported by the ceiling grid
ELE08-00195 Electrical Rough-In2/15/20082/19/20082/19/2008 9:11:41 AMANR
Scheduled by a contractor via Hello! on 2/15/2008 at 4:38:28 PM. Contact: ###-####. conf nec400.8 (bug zappers) & no cables shall be supported by the ceiling grid
ELE08-00194 Electrical Rough-In2/15/20082/19/20082/19/2008 9:10:20 AMANR
Scheduled by a contractor via Hello! on 2/15/2008 at 4:37:04 PM. Contact: ###-####. conf nec400.8 (bug zappers) & no cable shall be supported by the ceiling grid