FIR10-00066
| INSP-Final Inspection | 2/19/2010 | 2/19/2010 | 2/19/2010 3:49:41 PM | P | PASS |
|
|
Permit finaled
|
FIR10-00065
| INSP-Final Inspection | 2/19/2010 | 2/19/2010 | 2/19/2010 3:31:44 PM | P | PASS |
|
|
Permit finaled.
|
BLD09-00244
| FIRE-Final Inspection | 2/19/2010 | 2/19/2010 | 2/19/2010 3:28:49 PM | P | FAIL |
|
|
See a list of corrections listed on the back of the city approved fire plan review comments. They include posting the building address, providing an additional exit discharge light from Dining 126, posting the occupant load sign in Dining 126, mounting the K class fire extinguisher....ect
|
FIR09-00641
| INSP-Alarm Testing | 2/19/2010 | 2/19/2010 | 2/19/2010 3:20:00 PM | P | FAIL |
|
|
The testing and inspection is complete except for resubmittals showing all of the changes including wall mount a/v's and the additional common area smoke detectors/av's in the new "rehab" room. The door holder circuit and the hvac shutdown was repaired while I was on site.
|
BLD09-02009
| FIRE-Final Inspection | 2/19/2010 | 2/19/2010 | 2/19/2010 1:18:44 PM | P | PASS |
|
|
Life safety passed.
|
FIR10-00067
| INSP-Final Inspection | 2/19/2010 | 2/19/2010 | 2/19/2010 12:54:43 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00440
| INSP-Final Inspection | 2/18/2010 | 2/19/2010 | 2/19/2010 12:46:20 PM | A | PASS |
|
|
Permit finaled
|
FIR09-00708
| INSP-Sprinkler Rough-in/Hydro | 2/18/2010 | 2/19/2010 | 2/19/2010 10:23:40 AM | A | FAIL |
|
|
The last dry and wet system overhead hydro tests failed again. Will need to try again.
|
FIR09-00707
| INSP-Sprinkler Rough-in | 2/18/2010 | 2/19/2010 | 2/19/2010 10:15:31 AM | A | PASS |
|
|
See the city approved plans for locations where the sprinkler piping can be covered. They have been marked in red.
|
FIR10-00063
| INSP-Sprinkler Rough-in | 2/18/2010 | 2/19/2010 | 2/19/2010 10:10:58 AM | A | PART |
|
|
The sprinkler piping rough-in is passed but the piping can not be covered until the insulation that is hanging from the deck has been repaired.
|