ELE15-00432
| Electrical Rough-In | 2/18/2015 | 2/19/2015 | 2/19/2015 2:08:19 PM | P | PASS |
|
|
Wall Inspection. Geoff Hannaford is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce OK to cover walls, 1 room internal in warehouse area, power to 2 indoor AC wall mount units, conduit through wall to exterior units
|
ELE15-00050
| Final | 2/18/2015 | 2/19/2015 | 2/19/2015 1:25:45 PM | P | PASS |
|
|
Please call 20 minutes prior to .so we can get you into the office Eddy at ###-#### Phone #: ###-#### Inspection requested via web by Eddy Udry Final OK
|
ELE13-02226
| Electrical Rough-In | 2/19/2015 | 2/19/2015 | 2/19/2015 1:03:55 PM | P | NH |
|
|
Dean Phone #: ###-####// please call before left message at phone number provided at 12:50, stopped at site at 1:05, no access
|
ELE15-00442
| Final | 2/19/2015 | 2/19/2015 | 2/19/2015 12:50:43 PM | P | FAIL |
|
|
I am trying to get an energize service for this house. I did not see it in the drop down menu so I checked final Phone #: ###-#### Inspection requested via web by Jason Wicks 250.24 Grounding electrode system required 408.41 each grounded conductror shall terminate in an individual terminal that is als not used for another conductor 210.4 B Multi wire branch circuits shall be supplied with a means to disconnect all ungrounded conductors simultaneously 408.36 D Backfed devices shall be secured in place by additional means 250.104 Metal water piping shall be bonded 110.26 Working space for electrical equipment to be maintained, 3 foot clearance required 334.15 Romex shall be protected from physical damage BCC. 4-05-32 Known code violations not to be retained. When altering a pre-existing electrical wire, equipment, apparatus or fixture, or adding any new wiring, the existing electrical wiring in close proximity shall be in accordance with the present code 250.24.5 Load side gronding connections, grounded conductor shall not be connected to non current carrying metal parts, seperated neutral and ground at subpanel IDPCO contacted to place lock on meter, as seal has been removed
|
ELE14-01182
| Electrical Rough-In | 2/19/2015 | 2/19/2015 | 2/19/2015 9:48:00 AM | A | PASS |
|
|
rough in wall I.T. area. Shane is the contact his cell is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Walls OK to cover in IT area, there will be one more outlet added in office on wall that seperates office and closet when wall is replaced
|
ELE15-00436
| Temporary Service | 2/18/2015 | 2/19/2015 | 2/19/2015 9:09:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn T/S, U/G, N, OK
|
ELE15-00435
| Temporary Service | 2/18/2015 | 2/19/2015 | 2/19/2015 9:08:52 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn T/S, U/G, N, OK
|
ELE15-00358
| Rough-In Permanent Service | 2/18/2015 | 2/19/2015 | 2/19/2015 9:08:12 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn RI OK, P/S, U/G, N, OK
|
ELE15-00377
| Temporary Service | 2/19/2015 | 2/19/2015 | 2/19/2015 8:41:05 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk T/S, O/H, N, OK
|
ELE10-02400
| Final | 2/13/2015 | 2/19/2015 | 2/19/2015 8:33:06 AM | A | PASS |
|
|
Home owner request as close to 8:30 AM as possible. Please call Pam at 1-###-#### Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|