Inspections for the day of: Thursday, February 19, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00432 Electrical Rough-In2/18/20152/19/20152/19/2015 2:08:19 PMPPASS
Wall Inspection. Geoff Hannaford is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
OK to cover walls, 1 room internal in warehouse area, power to 2 indoor AC wall mount units, conduit through wall to exterior units
ELE15-00050 Final2/18/20152/19/20152/19/2015 1:25:45 PMPPASS
Please call 20 minutes prior to .so we can get you into the office
Eddy at ###-#### Phone #: ###-#### Inspection requested via web by Eddy Udry
Final OK
ELE13-02226 Electrical Rough-In2/19/20152/19/20152/19/2015 1:03:55 PMPNH
Dean Phone #: ###-####// please call before
left message at phone number provided at 12:50, stopped at site at 1:05, no access
ELE15-00442 Final2/19/20152/19/20152/19/2015 12:50:43 PMPFAIL
I am trying to get an energize service for this house. I did not see it in the drop down menu so I checked final Phone #: ###-#### Inspection requested via web by Jason Wicks
250.24 Grounding electrode system required
408.41 each grounded conductror shall terminate in an individual terminal that is als not used for another conductor
210.4 B Multi wire branch circuits shall be supplied with a means to disconnect all ungrounded conductors simultaneously
408.36 D Backfed devices shall be secured in place by additional means
250.104 Metal water piping shall be bonded
110.26 Working space for electrical equipment to be maintained, 3 foot clearance required
334.15 Romex shall be protected from physical damage
BCC. 4-05-32 Known code violations not to be retained. When altering a pre-existing electrical wire, equipment, apparatus or fixture, or adding any new
wiring, the existing electrical wiring in close proximity shall be in accordance with the present
code
250.24.5 Load side gronding connections, grounded conductor shall not be connected to non current carrying metal parts, seperated neutral and ground at subpanel
IDPCO contacted to place lock on meter, as seal has been removed
ELE14-01182 Electrical Rough-In2/19/20152/19/20152/19/2015 9:48:00 AMAPASS
rough in wall I.T. area. Shane is the contact his cell is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Walls OK to cover in IT area, there will be one more outlet added in office on wall that seperates office and closet when wall is replaced
ELE15-00436 Temporary Service2/18/20152/19/20152/19/2015 9:09:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
T/S, U/G, N, OK
ELE15-00435 Temporary Service2/18/20152/19/20152/19/2015 9:08:52 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
T/S, U/G, N, OK
ELE15-00358 Rough-In Permanent Service2/18/20152/19/20152/19/2015 9:08:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
RI OK, P/S, U/G, N, OK
ELE15-00377 Temporary Service2/19/20152/19/20152/19/2015 8:41:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
T/S, O/H, N, OK
ELE10-02400 Final2/13/20152/19/20152/19/2015 8:33:06 AMAPASS
Home owner request as close to 8:30 AM as possible. Please call Pam at 1-###-#### Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok