FIR14-00793
| INSP-Sprinkler Rough-in | 2/18/2015 | 2/19/2015 | 2/19/2015 3:30:05 PM | P | PASS |
|
|
UG/Flush passed. I noted the possible need for branch line restraints and plan modifications if the four additional elbows on the branchlines have not been included in the hydraulic calculations
|
FIR15-00040
| INSP-Sprinkler Rough-in | 2/19/2015 | 2/19/2015 | 2/19/2015 3:12:16 PM | P | PASS |
|
|
Hard lids ok to cover
|
BLD14-03618
| FIRE-Final Inspection | 2/19/2015 | 2/19/2015 | 2/19/2015 3:11:46 PM | P | PASS |
|
|
Life safety passed
|
BLD14-03617
| FIRE-Final Inspection | 2/19/2015 | 2/19/2015 | 2/19/2015 3:11:27 PM | P | PASS |
|
|
Life safety passed
|
BLD15-00019
| FIRE-Final Inspection | 2/18/2015 | 2/19/2015 | 2/19/2015 3:11:06 PM | A | FAIL |
|
|
Need city approved plans. Exit signs and emergency lights tested ok except for one near the main exit. It can be repaired or removed.
|
FIR14-00915
| INSP-Final Inspection | 2/18/2015 | 2/19/2015 | 2/19/2015 2:25:31 PM | P | CANC |
|
|
A separate contractor needs to pull a permit for the dialer which this fire alarm system is using to contact central station. No testing was performed.
|
FIR14-00941
| INSP-Final Inspection | 2/19/2015 | 2/19/2015 | 2/19/2015 12:06:54 PM | P | PASS |
|
|
Permit finaled
|
BLD14-02362
| FIRE-Final Inspection | 2/18/2015 | 2/19/2015 | 2/19/2015 10:43:47 AM | A | PART |
|
|
Life safety passed in the new two story addition. This includes the stand alone elevator recall.
|
BLD14-03531
| FIRE-Final Inspection | 2/18/2015 | 2/19/2015 | 2/19/2015 9:46:50 AM | A | PASS |
|
|
Life safety passed. Contractor to rplace missing exit discharge light at the main exit.
|
FIR15-00118
| INSP-Final Inspection | 2/18/2015 | 2/19/2015 | 2/19/2015 8:42:22 AM | A | PASS |
|
|
Permit finaled
|
FIR15-00011
| INSP-Final Inspection | 2/18/2015 | 2/19/2015 | 2/19/2015 8:39:34 AM | A | PASS |
|
|
Permit finaled
|
FIR15-00118
| INSP-Sprinkler Rough-in/Hydro | 2/18/2015 | 2/19/2015 | 2/18/2015 4:59:41 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Gobler Inspection cancelled from web by: Robert Gobler
|