Inspections for the day of: Friday, February 19, 2016.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03385 Final2/19/20162/19/20162/19/2016 2:17:48 PMPPASS
Mike// please call 30min prior Phone #: ###-#### final ok
ELE14-00532 Final2/19/20162/19/20162/19/2016 2:02:09 PMPFAIL
Ben Phone #: ###-#### 210.12 AFCI protection required for bedrooms 314.20 in walls with tile all boxes shall have a listed extender installed 406.4(d) replacing of receptacles shall be tamper resistant 334.30 type NM cable shall be supported 408.4 circuit directory required for panel board
ELE15-03744 Final2/19/20162/19/20162/19/2016 1:27:48 PMPCANC
Phone #: ###-#### Inspection requested via web by Emmet Bushman waiting for Idaho Power to lower attachment point below coupling on the over head mast
ELE15-00629 Final2/19/20162/19/20162/19/2016 1:04:06 PMPFAIL
Shane-please call meet for access Phone #: ###-#### 210.8 GFCI protection for all receptacles serving counter top 210.12 AFCI for all bedrooms @ smokes 406.4(d)(6) all outdoor receptacles shall be weather resistant and have a listed cover 330.30 MC shall be supported with 12" of a box 334.12 type NM cable shall ot be installed in a wet location 210.4(b) multi wire branch circuits shall open all ungrounded conductors 422.31 disconecting for fixed appliances need lockouts 314.25 blanks needed on open boxes 408.38 panelboards shall be deadfronted
ELE16-00451 Electrical Rough-In2/19/20162/19/20162/19/2016 12:13:44 PMPCANC
Phone #: ###-#### Inspection requested via web by shane miller
ELE16-00451 Rough-In Permanent Service2/19/20162/19/20162/19/2016 12:13:34 PMPPASS
Phone #: ###-#### Inspection requested via web by shane miller u/g from detached garage to house ok cover detached garage ok cover p/s o/h rec ok
ELE13-01121 ELE-Aging Inspection2/19/20162/19/20162/19/2016 11:25:51 AM PASS
called and left a message with Adam
ELE16-00458 Rough-In Permanent Service2/18/20162/19/20162/19/2016 11:03:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk rough-in ok cover p/s u/g n ok
ELE15-03017 Final2/18/20162/19/20162/19/2016 10:06:46 AMAFAIL
Please call Brent ###-####, when you are on your way. Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan 210.8 (a)(5) GFCI protection required for unfinished basements 334.15(b) type NM cable shall be protected from physical damage 334.12 type NM cable shall not be used in a wet location (a/c) 406.6 faceplate ccovers required
ELE15-03332 Electrical Rough-In2/19/20162/19/20162/19/2016 10:03:21 AMPCANC
We need a wall cover inspection. Thank You Dale Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Inspection cancelled from web by: Thomas Jenkins
ELE16-00453 Electrical Rough-In2/18/20162/19/20162/19/2016 9:39:21 AMAPASS
This is Rough in of a detached garage. Builder # is ###-#### Zac Smith. Phone #: ###-#### Inspection requested via web by Paula Gratiot 300.4 bored holes within 1 1/4 of framing member shall have nail plate 230.71 service discconect shall not have more then 6 means of disconnects
ELE16-00469 Rough-In Permanent Service2/17/20162/19/20162/19/2016 9:01:47 AMAPASS
Phone #: ###-#### Inspection requested via web by Emmet Bushman rough-in ok cover p/s u/g n ok