ELE15-03385
| Final | 2/19/2016 | 2/19/2016 | 2/19/2016 2:17:48 PM | P | PASS |
|
|
Mike// please call 30min prior Phone #: ###-#### final ok
|
ELE14-00532
| Final | 2/19/2016 | 2/19/2016 | 2/19/2016 2:02:09 PM | P | FAIL |
|
|
Ben Phone #: ###-#### 210.12 AFCI protection required for bedrooms 314.20 in walls with tile all boxes shall have a listed extender installed 406.4(d) replacing of receptacles shall be tamper resistant 334.30 type NM cable shall be supported 408.4 circuit directory required for panel board
|
ELE15-03744
| Final | 2/19/2016 | 2/19/2016 | 2/19/2016 1:27:48 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman waiting for Idaho Power to lower attachment point below coupling on the over head mast
|
ELE15-00629
| Final | 2/19/2016 | 2/19/2016 | 2/19/2016 1:04:06 PM | P | FAIL |
|
|
Shane-please call meet for access Phone #: ###-#### 210.8 GFCI protection for all receptacles serving counter top 210.12 AFCI for all bedrooms @ smokes 406.4(d)(6) all outdoor receptacles shall be weather resistant and have a listed cover 330.30 MC shall be supported with 12" of a box 334.12 type NM cable shall ot be installed in a wet location 210.4(b) multi wire branch circuits shall open all ungrounded conductors 422.31 disconecting for fixed appliances need lockouts 314.25 blanks needed on open boxes 408.38 panelboards shall be deadfronted
|
ELE16-00451
| Electrical Rough-In | 2/19/2016 | 2/19/2016 | 2/19/2016 12:13:44 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by shane miller
|
ELE16-00451
| Rough-In Permanent Service | 2/19/2016 | 2/19/2016 | 2/19/2016 12:13:34 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by shane miller u/g from detached garage to house ok cover detached garage ok cover p/s o/h rec ok
|
ELE13-01121
| ELE-Aging Inspection | 2/19/2016 | 2/19/2016 | 2/19/2016 11:25:51 AM | | PASS |
|
|
called and left a message with Adam
|
ELE16-00458
| Rough-In Permanent Service | 2/18/2016 | 2/19/2016 | 2/19/2016 11:03:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk rough-in ok cover p/s u/g n ok
|
ELE15-03017
| Final | 2/18/2016 | 2/19/2016 | 2/19/2016 10:06:46 AM | A | FAIL |
|
|
Please call Brent ###-####, when you are on your way. Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan 210.8 (a)(5) GFCI protection required for unfinished basements 334.15(b) type NM cable shall be protected from physical damage 334.12 type NM cable shall not be used in a wet location (a/c) 406.6 faceplate ccovers required
|
ELE15-03332
| Electrical Rough-In | 2/19/2016 | 2/19/2016 | 2/19/2016 10:03:21 AM | P | CANC |
|
|
We need a wall cover inspection. Thank You Dale Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Inspection cancelled from web by: Thomas Jenkins
|
ELE16-00453
| Electrical Rough-In | 2/18/2016 | 2/19/2016 | 2/19/2016 9:39:21 AM | A | PASS |
|
|
This is Rough in of a detached garage. Builder # is ###-#### Zac Smith. Phone #: ###-#### Inspection requested via web by Paula Gratiot 300.4 bored holes within 1 1/4 of framing member shall have nail plate 230.71 service discconect shall not have more then 6 means of disconnects
|
ELE16-00469
| Rough-In Permanent Service | 2/17/2016 | 2/19/2016 | 2/19/2016 9:01:47 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman rough-in ok cover p/s u/g n ok
|