Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00099 INSP-Final Inspection2/19/20162/19/20162/19/2016 3:19:58 PMPPASS
Final fire sprinkler inpsection passed/complete, project address located at 119 Broadway Ave, Boise ID.
FIR15-00235 INSP-Sprinkler Rough-in/Hydro2/18/20162/19/20162/19/2016 11:23:29 AMPPASS
hydrostatic test (200psi for 2 hours) passed/complete for underground fire supply main.
FIR15-00748 INSP-Sprinkler Rough-in2/17/20162/19/20162/19/2016 11:12:42 AMAPART
Rough to cover inspection complete for 1st and 2nd level, building A-2, overhead fire sprinkler piping approved for cover. Third level rough to cover inspection performed, inspection passed for rough-in, piping on third level cannot be covered until tenting/insulation inspection is completed.