MEC20-00685
| Rough-in | 2/19/2020 | 2/19/2020 | 2/19/2020 3:46:47 PM | P | PASS |
|
|
Please call contractor 30 minutes in advance for access at ###-#### and call Ryan with questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum -R/I ok
|
MEC20-00602
| Final | 2/18/2020 | 2/19/2020 | 2/19/2020 3:44:12 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette - final ok
|
MEC20-00699
| Final | 2/19/2020 | 2/19/2020 | 2/19/2020 3:00:51 PM | P | NH |
|
|
Inspection requested via web by Margie Rowe - no access left notice on front door
|
MEC20-00233
| Final | 2/12/2020 | 2/19/2020 | 2/19/2020 2:47:15 PM | P | PASS |
|
|
Homeowner Joel Santarone ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - final ok
|
MEC19-04898
| Rough-in | 2/19/2020 | 2/19/2020 | 2/19/2020 2:25:11 PM | P | PART |
|
|
301 - vent pipe clearances to framing ok - need to see clearances with insulation installed - vent piping specs should be followed for enclosure. having an access door to the vent and a b vent tee at the bottom for clean out
|
MEC20-00300
| Rough-in | 2/19/2020 | 2/19/2020 | 2/19/2020 2:07:31 PM | P | FAIL |
|
|
This is a duct work inspection only. Joe our installer will be there from 8:15 am -2 pm Phone #: ###-#### Inspection requested via web by Devry King - changes to HVAC need to be submitted to city for review - will need to see gas pressure test on new gas line - water heater flue needs 1" clearances and insulation shield installed - exhaust fans in showers need installed
|
MEC20-00613
| Final | 2/18/2020 | 2/19/2020 | 2/19/2020 1:18:40 PM | P | FAIL |
|
|
Please call ahead to Ben when headed to residence. He will not be home until 12:30pm Phone #: ###-#### Inspection requested via web by Sarah Small - A/C fuses need to 25 amp - A/C service port locking caps - pictures of corrections will be acceptable
|
MEC20-00444
| Rough-in | 2/18/2020 | 2/19/2020 | 2/19/2020 11:01:12 AM | A | FAIL |
|
|
insulation inspection Phone #: ###-#### Inspection requested via web by Dave Sorensen - outside air duct needs insulated
|
MEC20-00335
| Rough-in | 2/18/2020 | 2/19/2020 | 2/19/2020 10:41:53 AM | A | CANC |
|
|
consult - Cyrus Phone #: ###-#### Inspection requested via web by Brandon Sorensen
|
MEC20-00335
| Conference | 2/19/2020 | 2/19/2020 | 2/19/2020 10:41:44 AM | A | PASS |
|
|
consult - Cyrus Phone #: ###-#### Inspection requested via web by Brandon Sorensen
|
MEC19-05795
| Final | 2/18/2020 | 2/19/2020 | 2/19/2020 9:54:21 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lindsey Stegemann - fireplace final ok
|
MEC20-00476
| Final | 2/14/2020 | 2/19/2020 | 2/19/2020 9:53:58 AM | A | FAIL |
|
|
Call Chris in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout - A/C need locking caps - line set penetration into cover needs sealed - b vent needs 1" clearances - condensate line needs supported - will need install crew onsite to gain access to attic to furnace - talked with homeowner about getting a plumbing permit for plumbing vent that terminates in attic
|
MEC20-00692
| Rough-in | 2/18/2020 | 2/19/2020 | 2/19/2020 9:13:49 AM | A | FAIL |
|
|
Call for lock box code Phone #: ###-#### Inspection requested via web by Sean Hyten - all CSST in crawl needs supported per spec - need BTU information on range - only one appliance flex connector can be used on range gas line - gas piping connection to meter on north side looks to be under a car port and will need a crash bar/ protection post installed - 1/2 CSST gas pressure test fail gauge would not zero out - 5lb flue pressure test for water heater ok - 20lb gas pressure test to water heater ok
|
MEC20-00423
| Final | 2/18/2020 | 2/19/2020 | 2/19/2020 8:18:51 AM | A | PASS |
|
|
We sent pictures to Jack and he said he would pass it once he saw the corrections from the photos we sent. Phone #: ###-#### Inspection requested via web by Arielle Hendricks - final ok
|
MEC19-01851
| Mec-Aging Inspection | 2/19/2020 | 2/19/2020 | 2/19/2020 8:15:57 AM | | FAIL |
|
|
Permit has not been active since 5-10-19 when it passed a R/I inspection. Need to schedule final inspection with owner if ready. Permit will expire at next mechanical aging inspection if not active.
|
MEC19-03463
| Mec-Aging Inspection | 2/19/2020 | 2/19/2020 | 2/19/2020 8:14:25 AM | | PASS |
|
|
Doc Permit Finaled ok
|
MEC19-03463
| DOC - Permit Finaled | 2/19/2020 | 2/19/2020 | 2/19/2020 8:14:11 AM | A | PASS |
|
|
Doc Permit Finaled
|
MEC19-01842
| Mec-Aging Inspection | 2/19/2020 | 2/19/2020 | 2/19/2020 8:13:14 AM | | FAIL |
|
|
Permit has not been active since 5-31-19 when it failed final inspection. Add items to permit for final. Permit will expire at next mechanical aging inspection if not active.
|
MEC19-01841
| Mec-Aging Inspection | 2/19/2020 | 2/19/2020 | 2/19/2020 8:00:32 AM | | FAIL |
|
|
Permit has not been active since failing inspection on 7-5-19. If corrections have been made schedule inspection with owner. Permit will expire at next mechanical aging inspection if not active.
|
MEC19-01845
| Mec-Aging Inspection | 2/19/2020 | 2/19/2020 | 2/19/2020 7:58:10 AM | | PASS |
|
|
WIP
|