Inspections for the day of: Wednesday, February 2, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00337 Temporary Service2/1/20052/2/20052/2/2005 12:00:00 AMAFAIL
###-#### -george cor. posted called 110.26 needs clearence, 110.12(C) clean dirt and wasp nests from t/s 2/2/2005 11:00:34 AM
ELE05-00338 Permanent Service2/1/20052/2/20052/2/2005 12:00:00 AMAFAIL
Todd ###-#### need information called left message where is the p/s? no ID tag 2/2/2005 10:09:57 AM
ELE04-02628 Final2/1/20052/2/20052/2/2005 12:00:00 AMAPASS
joe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok card signed 2/2/2005 9:09:50 AM
ELE05-00314 Final2/1/20052/2/20052/2/2005 12:00:00 AMAPASS
Need inspection on wiring to new A/C unit. Everything located on outside. Internet Inspection Request from: Andy Rose ok 2/2/2005 10:29:45 AM
ELE05-00334 Rough-In Permanent Service2/1/20052/2/20052/2/2005 12:00:00 AMAPASS
zane ###-#### r/i 4 units ok
p/s u/g new ok 2/2/2005 8:27:36 AM
ELE05-00068 Rough-In Permanent Service2/1/20052/2/20052/2/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/1/2005 at 10:25:19 AM. Contact: ###-####. cor. and do not cover posted met contractor,310.15(B)(2)(a) derate conductorsin ENT,110.3(A) replace damaged MC, 250.24 terminate GRC at neutral bus not equip grd bus,362.26 shall not be more than 360 degrees of bends ENT250.70 shall use grd clamp listed for size GEC 620.23(A) shall provide seperate circuit for elevator machine rm lights and recepts soffit only ok for cover reinspection fee due posted 2/2/2005 2:51:29 PM
ELE05-00318 Final1/31/20052/2/20052/2/2005 12:00:00 AMPPASS
We put a box extension on the existing garage light and extended EMT with a second box for a new second light.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok 2/2/2005 12:49:18 PM
ELE05-00341 Electrical Rough-In2/1/20052/2/20052/2/2005 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 2/1/2005 at 4:43:22 PM. Contact: ###-####. walls ok 2/2/2005 3:21:27 PM
ELE05-00179 Permanent Service2/2/20052/2/20052/2/2005 12:00:00 AMPPASS
dan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok p/s o/h rec. see added r/i 2/2/2005 4:24:17 PM
ELE05-00344 Rough-In Permanent Service2/2/20052/2/20052/2/2005 12:00:00 AMPPART
Please call at least 20 mins prior to inspection///Rick; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called left message 2/2/2005 12:25:20 PM r/i ok, met with contractor needs grd rods and water system grd at p/s no sms, needs neutral and equip grd kits for p/s switch no violations retained note p/s was done without permit awhile back 2/2/2005 1:31:19 PM
ELE05-00179 Electrical Rough-In2/2/20052/2/20052/2/2005 12:00:00 AMPFAIL
cor. posted B C C violations not to be retained,, all new romex install without permit or inspection, done by prior owner shall not be used for commercial wiring. met with contractor, told him in phone conference prior to inspection, also told him we do not design, or tell them how to do the job