ELE05-00337
| Temporary Service | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | FAIL |
|
|
###-#### -george cor. posted called 110.26 needs clearence, 110.12(C) clean dirt and wasp nests from t/s 2/2/2005 11:00:34 AM
|
ELE05-00338
| Permanent Service | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | FAIL |
|
|
Todd ###-#### need information called left message where is the p/s? no ID tag 2/2/2005 10:09:57 AM
|
ELE04-02628
| Final | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PASS |
|
|
joe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok card signed 2/2/2005 9:09:50 AM
|
ELE05-00314
| Final | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PASS |
|
|
Need inspection on wiring to new A/C unit. Everything located on outside. Internet Inspection Request from: Andy Rose ok 2/2/2005 10:29:45 AM
|
ELE05-00334
| Rough-In Permanent Service | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PASS |
|
|
zane ###-#### r/i 4 units ok
p/s u/g new ok 2/2/2005 8:27:36 AM
|
ELE05-00068
| Rough-In Permanent Service | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/1/2005 at 10:25:19 AM. Contact: ###-####. cor. and do not cover posted met contractor,310.15(B)(2)(a) derate conductorsin ENT,110.3(A) replace damaged MC, 250.24 terminate GRC at neutral bus not equip grd bus,362.26 shall not be more than 360 degrees of bends ENT250.70 shall use grd clamp listed for size GEC 620.23(A) shall provide seperate circuit for elevator machine rm lights and recepts soffit only ok for cover reinspection fee due posted 2/2/2005 2:51:29 PM
|
ELE05-00318
| Final | 1/31/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PASS |
|
|
We put a box extension on the existing garage light and extended EMT with a second box for a new second light.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok 2/2/2005 12:49:18 PM
|
ELE05-00341
| Electrical Rough-In | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 2/1/2005 at 4:43:22 PM. Contact: ###-####. walls ok 2/2/2005 3:21:27 PM
|
ELE05-00179
| Permanent Service | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PASS |
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok p/s o/h rec. see added r/i 2/2/2005 4:24:17 PM
|
ELE05-00344
| Rough-In Permanent Service | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PART |
|
|
Please call at least 20 mins prior to inspection///Rick; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called left message 2/2/2005 12:25:20 PM r/i ok, met with contractor needs grd rods and water system grd at p/s no sms, needs neutral and equip grd kits for p/s switch no violations retained note p/s was done without permit awhile back 2/2/2005 1:31:19 PM
|
ELE05-00179
| Electrical Rough-In | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | FAIL |
|
|
cor. posted B C C violations not to be retained,, all new romex install without permit or inspection, done by prior owner shall not be used for commercial wiring. met with contractor, told him in phone conference prior to inspection, also told him we do not design, or tell them how to do the job
|